资源描述
光伏系统的防逆流控制,内容提要,一、背景概况,二、原理分析,三、关键技术,四、实验数据,五、结论感想,背景概况,上海闵行航天城,2.3MW,光伏停车场示范电站,并网不上网,300ms,切断逆流,关键技术,直流采样,电网侧功率突变情况,60kW,25kW,100kW,25kW,60kW,5kW,采样电路感应时间,97ms,177ms,310ms,切断逆流时间,247ms,327ms,460ms,电容放电,RC常数,111ms,128ms,125ms,测量功率(,kW),100,60,25,5,输出电压(,V),0.16,0.1,0.04,0.008,关键技术,交流,采样,关键技术,干节点通信,经过逻辑运算,判断出光伏电力逆流时,防逆流控制箱(检测部件)通过干节点通信,给防逆流控制器(执行部件)发信号,直接切断内部的触发器,从而切断光伏电力。,数据分析,直流采样,测试点,b,(黄色通道),测试点,a,(蓝色通道),数据分析,交流采样与干节点:逆流,切断时间试验,负载突变:,200kW,0kW,负载突变:,360kW,0kW,数据分析,交流采样与干节点:逆流,切断时间试验,序号,负载,逆变器启动,状态,P,控制,电网侧,功率,负载突变情况,电网侧,逆流功率,逆流切断,时间,1,360kW,3*100kW,50kW,56kW,负载全部切断,300kW,133ms,2,360kW,2*100kW,50kW,145kW,负载全部切断,200kW,128ms,3,360kW,1*100kW,50kW,238kW,负载全部切断,100kW,131ms,4,260kW,2*100kW,50kW,64kW,负载全部切断,200kW,133ms,5,200kW,100kW+10kW,50kW,95kW,负载全部切断,110kW,133ms,6,200kW,100kW+50kW,50kW,58kW,负载全部切断,150kW,115ms,7,200kW,100kW+30kW,50kW,72kW,负载全部切断,130kW,123ms,试验现场,结论感想,满足了电力公司,300ms,以内切断逆流的要求,具有有功功率调节功能,结论,感想,希望防逆流控制器退出历史舞台,We returned to Earth from space.,Thanks!,
展开阅读全文