1、 通信局(站)低压配电系统用电涌 保护器检查实行细则 目 录 1 编制依据及合用范围 ···························································································· 1 2 引用标准 ································
2、·················································································· 1 3 检查项目及技术规定····························································································· 1 3.1 检查项目及技术规定····················································································· 1 3.
3、2 对各种类型SPD 检测项目········································································· 7 4 检查方法·················································································································· 9 5 抽样 ·············································································
4、············································ 9 5.1 抽样基数········································································································· 9 5.2 样品数量········································································································· 9 6 质量鉴定 ········
5、········································································································· 9 6.1 通信局(站)低压配电系统用电涌保护器监督总体的检查项目和质量鉴定 ····················································································································· 9 6.2 鉴定准则······················
6、···················································································· 9 通信局(站)低压配电系统用电涌保护器检查实行细则 1 编制依据及合用范围 本实行细则依据YD/T1235.1-2023《通信局(站)低压配电系统用电涌保护器技术规定》编制。 本细则合用于通信局(站)低压配电系统用电涌保护器的质量检查。 2 引用标准 GB/T4942-1993 低压电器外壳防护
7、等级(eqv IEC60947:1988) YD/T1235.2-2023 通信局(站)低压配电系统用电涌保护器测试方法 3 检查项目及技术规定 3.1 检查项目及技术规定(见表1至表10) 表1检查项目及技术规定 序号 项目名称 技术规定 1 外观质量 a)电涌保护器表面应平整、光洁、无划伤、无裂痕及变形,紧固件应牢固,颜色应均匀无明显差异。 b)标志应完整清楚、耐久可靠,内容完全,且铭牌不应出现移动和任何翘曲现象。 2 保护模式 交流SPD必须具有N-PE、L-PE或L-N-PE的保护模式;直流SPD必须具有V+-V-的保护模式。 交流SPD宜具有L-N的保
8、护模式; 直流SPD宜具有V+-PE或V--PE的保护模式。 3 分离装置 SPD在故障或失效时,应有与电源系统永久断开的分离装置。 4 告警功能 SPD正常或故障时,应有能对的表达其状态的标志或指示灯。 SPD宜具有远程集中监测或集中告警的接口。 5 接线端子连接导体的能力 SPD的接线端子除应符合GB17464的规定外,其连接导线的能力还应符合表2或表3的规定。 6 最大连续运营电压 在70±3℃的实验环境下,施加规定的Uc连续48h,SPD应满足下列规定: a) 实验过程中,SPD应能稳定地正常工作、没有可见可闻的损坏; b) 实验前后的限制电压和点火电压
9、应小于UP,且限制电压的变化率不应大于±5%; c) 实验过程中,SPD的分离装置不应动作。 7 电压保护水平 SPD的电压保护水平UP应符合制造商所规定的数值。 8 等级限制电压 施加表4规定的等级测试电流IB时,限压特性的SPD的等级限制电压UB应符合表4的规定。 9 动作负载实验 在最大连续运营电压Uc下,SPD应能耐受规定波形、幅值和次数的冲击电流而不发生实质性损坏。SPD的雷击动作负载实验通过的判据如下: a) 在预备性实验和动作负载实验期间的每次冲击后,SPD都应能满足热平衡的规定; b)SPD应能自行遮断实验中产生的任何续流; c) 实验中SPD应不出现
10、击穿、闪络或机械损伤等现象; d)实验前后的限制电压和点火电压均应小于UP; e)实验中SPD的告警或分离装置不应动作。 10 电气间隙和爬电距离 电气间隙和爬电距离应符合表5的规定。 11 外壳防护等级 SPD的外壳防护等级(IP代码)应符合GB4942.2中规定的IP2LX。 12 保护接地 a)SPD在按正常使用条件安装和连接时,其非带电的易触及的金属部件(用于固定基座、罩盖、 铆钉、铭牌等以及与带电部件绝缘的小螺钉除外)应连接成一个整体后与保护接地端子可靠连接; b)保护接地端子螺钉的尺寸应不小于M4; c)保护接地应采用符合国标的标记加以辨认,如:字母标记
11、PE,图形符号〨等。 13 着火危险性(灼热丝实验) SPD的绝缘部件必须有足够的阻燃能力。绝缘部件在进行表6规定的灼热丝实验时,试品在下列情况可看作通过了实验: ——没有可见的火焰或连续火光; ——灼热丝移开后,试品上的火焰或火光在30s内自行熄灭,并且不应点燃实验用的铺底层中的薄绵纸(绢纸)、或烧焦松木板。 14 暂时过电压失效安全性 安装在L-PE或N-PE之间的SPD,在施加表7规定的异常的暂时过电压UT条件下,SPD故障时应具有安全的失效模式,实验期间不能点燃薄绵纸或粗绵布。 15 暂时过电压耐受特性 安装在L-PE或L-N之间的SPD应能耐受表8规定的暂态过电
12、压UT,并满足如下技术规定: a) UT断开后,SPD在Uc下应能达成热平衡; (注:假如在施加Uc的最后15min内,SPD的功耗或温度或流过SPD的阻性电流分量能稳定地减少,则认为SPD达成热平衡。) b) 实验后SPD的限制电压和点火电压均应小于UP; c) SPD的辅助电路,如状态指示灯应能正常地工作; 注:电涌保护电路以外的其它电路称为辅助电路。 d) SPD没有出现任何损坏的迹象。 16 热稳定性 按表9规定的每一实验电流等级进行的热稳定性实验时,SPD应满足如下规定: a) SPD连续通过每一档实验电流等级时,都应能达成热平衡或使其分离装置动作; 注:当电流
13、连续通过SPD时,10min内其温度的增长值小于2℃,则认为达成热平衡。 b)在实验期间,SPD的表面温度应始终低于120℃;分离装置动作后在5min内,SPD的表面温度应低于80℃。 c)假如SPD的分离装置动作,则相应SPD施加2Uc的工频电压,连续1min,此时应无超过0.5mAr.m.s的电流流过SPD。 17 电压降 a) 二端口交流SPD的L-N之间通过电阻性的额定负载电流IR时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降应不大于2%。 b)二端口直流SPD的V+-V-之间通过电阻性的额定负载电流IR时,在稳定条件下,同时测量的输入端口与输出端口之间的电压降
14、应不大于0.5%。 18 负载侧电涌耐受能力 二端口SPD的负载侧应能承受制造商规定的电涌电流的冲击。 19 负载侧短路耐受能力 在负载短路的条件下,二端口SPD应能承载制造商规定的短路电流。预期短路电流和功率因数应根据表10给出。实验结果的合格判据如下: a) 实验过程中,短路电流应在5s中断开,薄绵纸或粗绵布应不着火。此外,不应有爆炸或对人身或设施的其它危害发生。 b) 假如分离装置动作,则相应SPD施加2Uc的工频电压,连续1min,此时应无超过0.5mAr.m.s的电流流过SPD。 注:17,18,19 项不合用一端口SPD。 表2 一端口SPD接线端子允
15、许连接铜导线的标称截面积
SPD类型
能被夹紧的导线标称截面尺寸
mm2
交流SPD
T型
H型
M型
L型
25~50
16~35
10~25
4~16
直流SPD
H型
L型
4~16
2.5~6
表3 二端口SPD接线端子允许连接铜导线的标称截面积
额定负载电流IR
A
能被夹紧的导线标称截面尺寸
mm2
IR≤13
13 16、
16~35
25~50
注:
1 对于额定负载电流小于或等于50A的SPD,规定接线端子的结构能紧固实心导体以及硬性多股绞合导体,允许使用软导体。
2 二端口SPD接线端子连接导线的能力除应符合本表的规定外,还应根据其标称放电电流的大小,同时符合表3的规定。
表4 限压特性的SPD的等级限制电压UB
最大连续
运营电压
Uc
交流SPD的UB上限值(V)
直流SPD的UB上限值(V)
T型
( IB=60kA )
H型
( IB=40kA )
M型
L型
( IB=5kA )
H型
( IB=5kA )
L型
( IB=2kA )
( I 17、B=25kA)
( IB=15kA )
45V
—
—
—
—
—
425
250
52V
—
—
—
—
—
450
275
75V
—
—
—
—
—
500
325
85V
—
—
—
—
—
550
350
275V
2600
2100
1600
1250
950
—
—
320V
2850
2300
1700
1450
1150
—
—
385V
3200
2600
2023
1800
1400
—
—
420V
3450
2800
2200
1900
160 18、0
—
—
460V
3700
3000
2500
2100
1750
—
—
510V
3950
3200
2700
2300
1900
—
—
600V
4400
3600
3100
2700
2300
—
—
表5 电气间隙和爬电距离
检 查 部 位
1) 接线端子不同相的带电导体之间。
2) 接线端子各相与:
接地端子、零线端子之间;
固定SPD的金属螺钉、外壳、机箱、面盖或其它金属工件之间。
SPD的Uc
<100V
100~200V
200~450V
450~600V
电气间隙和爬电距离(mm)
≥ 19、2
≥4
≥6
≥11
表6 SPD绝缘材料的灼热丝实验条件
实验绝缘零件
灼热丝顶端温度
℃
实验连续时间
s
支持或固定接线端子各相载流部件和保护电路部件的外部绝缘零件
850±15
30±1
不支持或固定载流部件的绝缘外壳、其它外部绝缘零件
650±10
30±1
注
1 就本实验而言,平面安装式SPD的机座可看作为外部零件。
2 对陶瓷材料制成的部件不进行本实验。
3 假如绝缘零件是由同一种材料制成,则仅对其中一个零件按相应的灼热丝实验温度进行本实验。
表7 TOV失效安全性实验条件
保护模式
暂时过电压
Vr.m.s
实验 20、连续时间
s
L-PE、N-PE
1200
5
表8 TOV耐受特性条件
保护模式
暂时过电压UT
Vr.m.s
实验连续时间
min
L-PE
380
120
L-N
320
120
表9 热稳定性实验电流等级
序号
1
2
3
4
5
6
实验电流等级mAr.m.s
5000
2500
1000
320
80
20
表10 预期短路电流(Ip)和功率因数(cosj)
Ip(kA)%
cosj()
Ip≤1.5
0.95
1.5 21、0
0.7
6.0 22、保护模式
√
√
√
√
√
√
3
分离装置
√
√
√
√
√
√
4
告警功能
√
√
√
√
√
√
5
接线端子连接导体的能力
√
√
√
√
√
√
6
最大连续运营电压
√
√
√
√
√
√
7
电压保护水平
√
√
√
√
√
√
8
等级限制电压
√
√
√
√
√
√
9
动作负载实验
√
√
√
√
√
√
10
电气间隙和爬电距离
√
√
√
√
√
√
表11(续). 通信局(站)低压配电系统用电涌保护 23、器测试项目
低压配电系统用电涌 保护器产品名称
检测项目名称
一端口单相交流浪涌保护器
二端口单相交流浪涌保护器
一端口三相交流浪涌保护器
二端口三相交流浪涌保护器
一端口直流浪涌保护器
二端口直流浪涌保护器
11
外壳防护等级
√
√
√
√
√
√
12
保护接地
√
√
√
√
√
√
13
着火危险性(灼热丝实验)
√
√
√
√
√
√
14
暂时过电压失效安全性
R
R
R
R
R
R
15
暂时过电压耐受特性
√
√
√
√
R
R
16
热稳定 24、性
√
√
√
√
√
√
17
电压降
√
√
√
18
负载侧电涌耐受能力
√
√
√
19
负载侧短路耐受能力
R
R
R
必须检测项目数
注:表中打“√”的检测项目为该产品必须进行的检测项目,打“R” 的检测项目为该产品参考检测项目。
4 检查方法
检查方法参考YD/T1235.2-2023《通信局(站)低压配电系统用电涌保护器测试方法》。
5 抽样
5.1 抽样基数:
——装配完整的电涌保护器整机(箱体):不少于8个;
——结构相同的保护单元( 25、模块):不少于25个。
5.2 样品数量:
——装配完整的电涌保护器整机:2个;
——结构相同的保护单元:9个。
6 质量鉴定
6.1 通信局(站)低压配电系统用电涌保护器监督总体的检查项目和质量鉴定(见表12)。
6.2 鉴定准则:产品出现1项B类不合格或多于2项C类不合格时,判该监督总体不合格。
表12 质量鉴定
序号
项目名称
不合格类别
B类
C类
1
外观质量
O
2
保护模式
O
3
分离装置
O
4
告警功能
O
5
接线端子连接导体的能力
O
6
最大连续运营电压
O
7
电压保护水平
O
8
等级限制电压
O
9
动作负载实验
O
10
电气间隙和爬电距离
O
11
外壳防护等级
O
12
保护接地
O
13
着火危险性(灼热丝实验)
O
14
暂时过电压失效安全性(参考项)
15
暂时过电压耐受特性(直流浪涌保护器为参考项)
O
16
热稳定性
O
17
电压降
O
18
负载侧电涌耐受能力
O
19
负载侧短路耐受能力(参考项)