Automatic self-cleaning filter Operation manual
Model CNAF-JT
Beijing Luolun (Excel Ethics) filtration Equipment technology Co., Ltd
1 Product introduction
Filtration is one important part of water purification, which filters the impurity in order to achieve the purpose of water treatment or protection. Traditional net filtration approaches have been widely applied in water treatment and industrial water recycling system owing to its good filtration result and small resistance. However, these approaches have the limit of volume of impurity to be treated, easily blocked and complicated cleaning process which must be cleaned after the whole system is disassembly. This kind of cleaning process loses the monitor and lowers the automation for whole system. Automatic cleaning filtration filters the grey water and automatically cleans the filter without stopping supplying the water. The system is fully automatic and treats big volume of grey water.
Picture 1
2 Serviceable range
JT- automatic self-cleaning filter widely applied in circle or acyclic cooling waters system, heat exchanging system, central air-conditioning system, and central heating system, hot-water boiler, which are used to protect cooling equipment, heating exchanging system, air condition and boiler. It is suitable to industry circulating water filtrations, such as steel system, petroleum chemical industry, metallurgy, electron, papermaking, food.
This equipment requests water temperature flow the filter can’t surpass 95℃.
The request of water quality: The suspended substance in water is smaller than 60mg/L, suspended substance can be allowed to achieve 110mg/L in the short adequate time. If the water quality cannot meet the requirements, it needs to pretreatment before enter to the inlet.
3 Product functions and characteristics
3.1 product functions
Automatic cleaning filtration system filters the grey water and automatically cleans the filter without stopping supplying the water.
The system has two control types: Manual and automatic.
Automatic control: There are two ways for automatic control. One is timer and the other is pressure difference. Set the time for the filtration on the timer. When it finishes the cleaning process starts automatically. In the meantime, the control system compares the system pressure difference with pre-set pressure difference. If both differences meet together the system starts the automatic cleaning. The duration is set by the timer. When the cleaning finishes the system goes back to the initial state and is ready for the next cycle.
Manual control: Turn the switch to the manual and it starts to clean the filter manually.
Customers can choose any model of control according to the need. Please see the details of operation in the operation section.
3.2 product Characteristics
1) The default filter fitness is 100 microns and optional from 100 microns to 3000 microns. Moreover, its filter area is large, the pollutional load is high, and user can setting according to actual working condition.
2) It is easy to operate automatic cleaning under the electronic monitor. All parameters for the control system can be adjusted.
3) The system has designed for the over-load motor protector.
4) The system features in non-stop supply of water when the cleaning is processed. It consumes little water to clean. The amount of water used is less than 1% of the total amount of water.
5) Easy to maintain and uninstall.
6) The system is designed French connection and easy.
4 Product model descriptions
JT-automatic self-cleaning filter’s specifications is distinguished by inside nominal diameter of water inlet and outlet, Conventional produces have twelve specifications: 3²、4²、5²、6²、8²、10²、12²、14²、16²、18²、20².PN=1.6MPa
Representation of the specifications as followed:
CNAF-JT
PN (MPa)
Inside nominal diameter(inch) model
Model
Automatic self-cleaning filter
For example: 10’’ JT- automatic self-cleaning filter can be expressed as CNAF-JT10-1.6
5 Product structure descriptions
As shown in picture 1, we adopt the mechanical-electrical integration system design
JT-automatic self-cleaning filter is made of driver, control circuit (including the switch of pressure difference), filtration, cleaning parts, French connection etc.
Electrical control, control circuit and discharge valve are the main parts for the control system which operates the automatic cleaning process.
Control circuit is made of switch of pressure difference, brass and
connection etc.
The filter is normally made of stainless steel and can be other options according to the water temperature and quality.
6 Product Outlook
1、mounting dimensions (as shown in picture 2)
Picture 2
2) Sharp chart,as shown in table 1
Table 1
Model
pipe diameter
J
J1
J2
Y
Y1
K
Weight
(inch)
mm
mm
mm
mm
mm
mm
(Kg)
CNAF-JT03
3
886
376
718
683
257
673
87
CNAF-JT04
4
936
411
770
683
257
673
106
CNAF-JT05
5
1018
461
852
683
257
673
132
CNAF-JT06
6
1111
523
951
744
303
725
197
CNAF-JT08
8
1427
715
1237
820
349
777
248
CNAF-JT10
10
1685
853
1439
874
393
826
360
CNAF-JT12
12
1815
944
1569
939
458
908
486
CNAF-JT14
14
2082
1094
1792
1026
545
1010
653
CNAF-JT16
16
2360
1239
2019
1098
608
1111
765
CNAF-JT18
18
2632
1389
2245
1199
679
1213
814
CNAF-JT20
20
2919
1547
2483
1288
717
1250
920
CNAF-JT24
24
3510
1865
2864
1458
864
1440
1038
7 technical performance parameters
Technical parameters and main construction size as shown in table 2:
model
parameter
JT
03
JT
04
JT
05
JT
06
JT
08
JT
10
JT
12
JT
14
JT
16
JT
18
JT
20
JT
24
working volt
alternating current 380V50Hz
power(kW)
0.25
0.25
0.25
0.25
0.37
0.37
0.37
0.55
0.75
0.75
2.20
2.20
Economic output (m³/h)
45
65
105
150
260
410
590
800
1050
1320
1630
2350
minimum operating pressure (MPa)
0.1
maximal operating pressure (MPa)
1.6
Filtering area (cm²)
1165
1367
2095
3014
5270
7867
11414
15552
20344
25751
31786
42295
Inlet and out let inside nominal diameter (mm)
DN80
DN100
DN125
DN150
DN200
DN250
DN300
DN350
DN400
DN450
DN500
DN600
wash water valve inside nominal diameter (mm)
DN50- DN80
the time for pollution discharge (s)
10~60
8 Matters need attention
The device has been debugged before leaving the factory, it can run directly while using. When the equipment parameters cannot satisfy the user request, the user can act according to the actual operating mode to set various parameters, or selects ways such as hand control, automatic timing control to carry on the work correspondingly.
When runs for the first time, please carry on according to the below step:
Inspects the filter whether to be at the normal work condition:
Whether the pollution discharge tube has been connected, length of blowdown pipe can’t surpass 15 meters, cannot have the upward inclination angle, in order to avoid has the back pressure.
Examine each joint whether reliable.
Examine that the electric cabinet is dry.
Power-on, the green power light turn bright, indicated that electrical controlled part is at the normal work condition, the equipment can put into service
Notes: maintain hands dry while inserts the electric power source. Meanwhile maintain electric control part is dry during the filter working, cannot let the water enter into.
9 Install and transport
9.1 Power connection
Please choose power socket following the hints about voltage and power on the nameplate, select 1.5 mm2 or 2 mm2 wire and switch-in input terminal to the bottom of the electrical cabinet, as shown in picture 3. Please install the triphase power according to the picture 3.
Picture 3
9.2 The connection about control box
(1) Electrical motor connection: The electrical motor triple-phase line switch-in U3, V3, and W3 separately; the groundwire switch-in PE. As shown in picture 4, they switch-in end board on the right of the electrically controlled box bottom.
(2) Solenoid pilot actuated valve connection: the red line switch-in the electrically controlled box 104 terminator, the black line to switch-in the electrically controlled box N terminator. The olivine lines switch-in the electrically controlled box PE terminator. As shown in picture 4, they switch-in end board on the right of the electrically controlled box bottom.
(3) Pressure gage switch connection: The NO terminator switch-in the electrically controlled box 102 terminator, the COM termination switch-in the electrically controlled box 108 terminator. As shown in picture 4, they switch-in end board on the right of the electrically controlled box bottom. Pressure switch
Solenoid pilot actuated valve
Electric motor
Picture 4
9.3 Installation and precaution
1) The arrow indicates the water flow direction. The filtration needs to be installed by this direction.
2) Sewage pipe should be French connected onto the water solenoid valve. The pipe should not be longer than 15 meters and no angles allowed in order to avoid the pressure difference.
3) There are two ways of filter installation. See Picture 5—7. Please note the water flow direction must be correct and the water solenoid valve should be installed at a horizontal level or at lower place in order to have a full cleaning.
Picture 5
Picture 6
4) The filter should use a tandem combination. To guarantee uninterrupted water supply when overhauling the device for water treatment, We suggest you established the bypass in the system, the inlet and outlet of filter and the bypass should install the cut-off to use the valve, for example: The cut-off valve, the reed valve and so on.
5) The selection of filter specification should match to the pipeline installation. For example: The system caliber is 10, thus you may choose filter of specification 10. When the flow rate cannot satisfy the pipeline requests, users may use the way of parallel connection, as shown in picture 7
Picture 7
6) The filter should install before the water equipment which system need to be protected, the installation should approach to the protected device as far as possible.
7) Install the check valve in the outlet of the filter in the place may cause backflow.
8) In the dynamic system, the filter should install between the pump and the equipment, more approaches the equipment to be better. If pressure between the pump and equipment surpasses filter's EP, should install the filter before the pump, and approach the pump as far as possible.
9) Installation of the electrical Controllers: When electric control leaving the plant, to be fixed according to default position. If the actual position is different from the default position, users can dismantle four erection bolts used fixed electric cabinet, after adjusting the electric cabinet bracket and electric cabinet’s correct direction, and then fix the four erection bolts.
10) Choose the reasonable installation environment, pay attention to waterproofing, rainproof, and moisture-proof.
11) Before leaving the plant, the products have been debugged, user should not disassemble or debug at will.
10 Operation
ST series has manual and automatic way of cleaning. The control panel is as follows in the picture 10.
Picture 10
10.1 Manual
Turn manual/auto to manual position. See picture 10. Motor and water control are connected to the power. The water valve opens and it stars to clean. Turn the manual/auto to auto the system goes into automatic process.
Manual control is a way to check whether the motor and water valve work properly. If the system can’t clean normally when it is under manual and it can’t do under auto.
10.2 Auto
Turn to auto position. Set the filtration time and cleaning time on timer. The set up figures are displayed in the bottom of the timer and the counting figures are displayed on the top of the timer.
Timer setting: Press the select button and the first digit pipe flashes. Press the “up” button to adjust the figure and press the select button. The second digit pipe flashes. Use this way to adjust all figures for the time. When the setting is done the digit pipe will flash 8 times and the figures are saved to the memory where all data won’t be lost even the power is off. Press the start button the timer begins to count the time. If the power is off the timer will count the time when the power is back next time.
The filtration time measures in minute. The maximum time is 9999 minutes. The cleaning time measures in second. The maximum time is 99.99 seconds. Turn to auto state when the power is on. The filtration process starts for a duration that sets in the timer. In the meanwhile the pressure difference switch also compares the pressure difference between the real situation and the figure that is set up initially. If the duration of time for filtration is up but the pressure differences haven’t met then the system also starts to open the cleaning valve and begin to clean. The time of cleaning is being counted. When the time of cleaning ends the cleaning valve closes. New cycle begins. In the other situation, if the of duration of time set on the timer hasn’t elapsed and the pressure differences have met each other then the system also open the cleaning valves and starts cleaning. The filter stops counting and cleaning process starts to count the time. The system will repeat the process time by time.
Picture 11
Adjustment of Pressure difference indicator (Picture 11)
The pressure difference indicator has been set in the factory and the pressure difference is 0.5 Bar. There is an adjusting screw on the low pressure end of the indicator. One clockwise turn increase the pressure difference by 0.06Bar. One anticlockwise turn decrease the pressure difference by 0.06Bar. E.g. If the current pressure difference is 0.5Bar and needs to be changed to 0.2Bar, 5 anticlockwise turns are needed. Vice versa.
Adjustment of pressure difference: the indicator can be uninstalled from the system and connect its high pressure end to the pressure-increase equipment and pressure meter if the indicator needs to be adjusted. Observe the movement of indicator. Increase the pressure to the figure needed on the high pressure end. E.g. 0.5Bar is needed for the pressure difference indicator. Turn the adjusting screw when the pressure meter reads 0.5Bar. If the screw moves to the figure of 0.5Bar it is the figure for the pressure difference indicator.
Service Promise
Beijing Luolun (Excel Ethics) filtration Equipment technology Co., regards quality and credit standing as life, insists on the corporate principle “Create with heart, Based on the market”. Aim at meeting