1、Lightning protection grounding construction scheme Preparation: Jiang da auspicious Reviewer: Xia Chengyou The approver Yang Rong Unit: HuaRen construction group co., LTD The first chapter project summary 一、Basic situation of engineering, This pr
2、oject is located in zhongshan city god bay town rainbow building knife island, a four layer yacht entry-exit inspection do comprehensive public building construction, building a total height of 11.9 m. Engineering basic information table: The name of the project The yacht entry-exit inspection
3、 building The construction site Sharpen shen wan town, zhongshan city rainbow road island The construction unit Zhongshan millennium Marine co., LTD Architectural design of the unit Architectural design institute co., LTD., zhongshan city, guangdong province Theconstructionsupervising uni
4、ts Zhongshan torch in supervision consulting co., LTD Qualitysupervisiondepartment Zhongshan city construction engineering quality surveillance Theconstruction time limit for a project 180 days The overall contractors HuaRen construction group co., LTD Professional construction unit
5、 Zhongshan city in hydropower room decoration co., LTD 二、Lightning protection grounding profiles The project according to the second class building lightningproof grounding design, roof lightning protection zone, downlead, earthing device and embedded parts are associated with the building stru
6、cture by heavy current professional responsible for completing the subcontract unit. The contractor is responsible for the coordination, cooperation and management of subcontractors grounding work. Lightning protection grounding system include: The name of the item Overview features Lightning
7、 protection zone The building roof set not greater than 10 x10m or 12 x8m lightning protection network. Glass curtain wall at the top of the metal frame must be connected with the lightning protection belt. On the roof of all metal bossed, ventilation pipe and so on lightning protection belt conn
8、ected with the roof, a total 12 0.6 meters tall, small flash needle. Roof electrical wiring in steel pipe and instead of distribution box, electrical equipment, metal casing connection, and connected to the lightning protection device to the nearest. Down lead This project use the column diagonal
9、 two root diameter greater than or equal to 16 main reinforcement jumper as down lead as lightning protection downlead welding. All down lead spacing is not more than 12 m and down lead and roof lightning protection devices must follow basic ground net.through forming pathway, the grounding resistan
10、ce is not greater than 1. Equipotential connection Layer distribution room set total equipotential terminal box, distribution box for a layer, low voltage room, all grounded in the structure of the metal pipes. Basic grounding Bottom moderators reinforcement and foundation reinforcement is
11、used as the grounding device. Electrical grounding, security, lightning protection grounding and other weak current systems share the grounding device. Joint earthing system grounding resistance shall not be greater than 1, in the position of the need to lead to ground connection panel, set on the o
12、utside of partly on the ground down lead test terminal. Lightning protection waves invasion All information and weak current equipment room and downlead post keep a certain distance, and shielding, grounding and equipotential connection, installing overvoltage protection within the system. Th
13、e low voltage into line ark and day face equipment distribution box, information and weak current equipment room power box, and other information equipment power box are set a surge protector. The second chapter compilation basis A, contract documents, and local laws and regulations 1, the li
14、ghtningproof grounding engineering drawings. 2, project contract documents. 3, the People's Republic of China promulgated by the current effective electrical engineering all kinds of rules, norms and test evaluation standard. 4, the corresponding industry standard, main laws, regulations and regu
15、latory documents. 5, the people's government of guangdong province management on construction projects, municipal administration, environmental protection and other laws and regulations. 6, ISO9000 quality management system, ISO14000 environment management system, OSHMS18000 occupational safety an
16、d health management system standard, my company's quality, environment and occupational safety and health management manual, program files and its supporting documents. 7, at the national level method and the enterprise can recommend focus on promotion of new technology and ministry of construction
17、 Second, the main standards, specifications, documents The name says Make no. "The green building evaluation standard" GB / t50378 - 2014 The project management of construction engineering GB/t50326-2006 The building engineering construction quality evaluation standard" GB/t50375-200
18、6 The construction quality acceptance of building electric installation engineering GB50303-2002 The electrical device installation and acceptance specification for construction of grounding device GB50169-2006 The building electronic information system lightning protection technology specif
19、ication" GB50343-2012 The building lightning protection engineering construction and quality acceptance specification" GB500601-2010 "Public building energy efficiency design standard" GB50189-2005 "Civil building design specification" JGJ16-2008 "Urban regional environmental noise stan
20、dards" GB3096-93 Construction machinery use safety technical specifications JGJ33-2012 Construction site temporary electricity safety technical specifications JGJ46-2014 Working construction of higher safety technical specifications JGJ80-1991 "The building electrical engineering constru
21、ction technology standard" ZJQ00-SG-006-2003 "The building electrical common data" 04DX101-1 Atlas of the lightning protection and grounding installation D501-1~4 Atlas of building electrical general (lightning protection and grounding device) 92DQ13 The third chapter construction method
22、 The construction sequence Material preparation and material acceptance - base earthing body welding - column NaZhu reinforcement to the layers of steel welding, welding roof lightning protection network (pin) - grounding resistance test - transfer welding First, the overall deployment The whole
23、 process of lightning protection construction with civil engineering structure, according to the civil engineering structure construction section thought lightning protection engineering mainly divided into the following stages: 1, the floor construction phase Insert time for floor construction ac
24、cording to construction progress, for lightning protection foundation construction process should be ground net.through together as a whole. In floor area construction, the edge of the area and other districts junction as lightning protection grounding network in the beam main reinforcement marked w
25、ith yellow paint, to ensure that the next area with the area reserved by landlord reinforcement construction accurate docking. 2, structure construction stage Construction stage according to the latest and the examination and approval of lightning protection downlead deepen drawing connections, bu
26、ilding lightning protection network welding. 3, lightning protection test in stages Grounding construction effect, in order to ensure that each stage of construction completion of all lightning protection test, such as the test is not qualified to remedy in a timely manner. Second, the constructi
27、on preparation 1, the machine to prepare Machine name model The number of Ac arc welder BX1-315 1Taiwan Cutting machine CJ-400 1Taiwan Grounding resistance tester (ZC - 8) 3.0 level,0.1-100Ω 1Taiwan Vernier caliper 0.02mm/0-300 1 the Steel tape 0-5m 4 the Test all equipmen
28、t comes into play, can be put into use after inspection; All machinery equipment selection Determined according to the actual situation, to ensure that can form a group work. In a timely manner in the process of construction steel binding insert lightning protection welding construction, ensure the
29、 quality and efficient complete welding, does not affect the civil concrete time. 2, personnel ready to (1) those responsible Mechanical and electrical department managers and professional quality inspectors as main monitors, mechanical and electrical department manager first responsible for ligh
30、tning protection grounding construction quality, safety. (2) the electrical engineer Requires supervision and guidance of construction personnel for the electrical professional engineers, have the builder certificate and license, grounding construction experience, can detailed technical clarificai
31、ton operating personnel and can guide the construction on site, the control quality. (3) materials Is responsible for issuing material inspection and storage in work, ensure all materials used on the site in compliance with national standards and design, the owner, supervision requirements. (4)
32、 welders Welding operation personnel must hold electrician special work license and welder special type of work license, on the floor and the work high above the welder must, must first be examined before mount guard, to ensure the healthy body rear can mount guard. Welding quality must meet the co
33、nstruction specification and owner, supervision, lightning protection departments acceptance requirements. All operators must be admission safety education and the construction safety technical disclosure, and access to the construction site for construction only after they have passed the examinat
34、ions. 3, technical preparation (1) Grounding the early stage of the construction drawings to deepen design according to requirements of the owners and design units, deepening the design after the completion of the audit submitted to the owner and design institute, approval by the rear can be used
35、as construction drawings. (2) On the basis of workers on site before the construction drawings disclosure and technical disclosure. Third, the main construction method 1, the basic ground net A layer of floor basement layer of the ground net according to have approval on the plane deepen design
36、basis for lightning protection construction, foundation grounding network using ground beam two root diameter greater than or equal to 16 mm steel and 50 * 4 hot dip galvanized flat iron welding forming grounding flat screen. 2, downlead (1) main reinforcement is used as the down lead inside wall
37、column The project used the column diagonal two main reinforcement is greater than or equal to 16 mm in diameter as lightning protection downlead, lightning protection downlead with reliable grounding network connection at the bottom and in the main muscle sleeve joint jumper with a diameter of 10
38、mm round steel. In the process of construction should not only strictly control the welding quality, but also to the value of the main reinforcement as downlead completes the logo with yellow paint, in order to avoid wrong welding short of lightning protection effect. Particular way is shown in figu
39、re 1. 3, lightning protection zone (1) The roof Roof roof lightning protection network, the use of phi 10 hot dip galvanized steel garden according to have approval to deepen the design drawings of dark apply within the roof top screed-coat, daughter on the wall of the lightning protection
40、 dark in the steel structure curtain wall keel laying of roof pressure, and a reliable connection with the steel structure curtain wall keel, all down lead onto the floor, the roof and the lightning protection network and roof and all roof above the metal phase connected. 4, local equipotential con
41、nection This project is using joint grounding method, all Shared grounding device, grounding and lightning protection grounding system common grounding device Ω resistance is not greater than 1. Equipotential connection after the installation guide connectivity test. (1) Distribution of well, tele
42、com equipment room, high voltage, low, such as pipeline access based on a layer of grounding deepen the position of the diagram in a layer of chassis ground reserved online 40 x 0.3 meters four hot dip galvanized flat steel plate, used by professional contractors. (2)According to the lightning prot
43、ection grounding deepening figure marked the location of the reserved 25 * 4 hot dip galvanized flat steel and equipotential connection terminal box of the mouth of the cave, cooperate with civil engineering construction in the late MEB and LEB terminal box installation. Reserved MEB and LEB termina
44、l board and grounding flat steel and reliable connection. (3) Total equipotential connection terminal board is a distribution box, ark inside layer distribution room; All into the structure of the metal line grounding connection. 5, grounding test According to design requirements, the constructio
45、n plan position set grounding test points, to facilitate later every year regularly test. Test points in the building is 500 mm, from outdoor ground test point location and eventually to examination and approval of the underlying grounding deepening figure shall prevail. Basic grounding network con
46、struction after the completion of the grounding resistance test, if can't meet the requirements, timely increase until the grounding body meet the requirements, the main structure completed a grounding resistance test, guarantee the grounding resistance under 1 Ω. Adopted ZC - 8 grounding resistanc
47、e tester docking ground resistance measurement, the measured resistance value should meet the design and specification requirements. Each local ground measurement times for at least 3 times, calculate the average data can be considered that point grounding resistance. Connection mode as shown in fig
48、ure 8. Four, the main control parameters 1, the joint earthing resistance is not greater than 1 Ω in any season. 2, the distance between the down lead shall not be greater than 12 m. 3, welding length: flat steel and flat steel lap length for larger models is 2 times of the width of the flat s
49、teel, three sides welds; Round steel and round steel welding for large type 6 times the diameter of the round steel, double sided welds; Round steel and flat steel lap weld length is 6 times the diameter of the round steel, double-sided welding. Double-sided welded construction do have some difficul
50、ty, one-side welding to extend lap multiples for overlap ratio of 2.5 times. Adopts the round steel structure steel jumper, weld length should be 6 times the diameter of the round steel, double-sided welding. 4, welding parameters monitoring (1) welding parameters: Power supply voltage: ~ 380 v