1、电缆型号与外径尺寸对照表(埋管必须资料)序号电缆型号电缆外径(mm)备注1YJV-6KV-3*1635.902YJV-10KV-3*2540.503YJV-10KV-3*3545.404YJV-10KV-3*9557.105YJV-10KV-3*24072.906VV3*240+1*12055.027VV3*185+1*9553.308VV3*120+1*7044.019VV3*95+1*5039.5210VV3*35+1*1627.0811VV3*25+1*1624.91YJV6/6KV、6/10KV 交联电缆技术参数YJV6/6KV、6/10KV 交联聚乙烯绝缘聚氯乙烯护套电力电缆导体标称
2、截面绝缘厚度护套厚度电缆近似外径电缆近似重量20导体电缆载流量短路电流直流电阻在空气中直埋土壤中导 体屏蔽层铜带铜丝mm 2mmmmmmkg/km/kmAAKAKAKA1253.41.8216850.7271651603.691.0833.5061353.41.8228070.5242051905.151.0823.5011503.41.8239770.3872452257.311.0793.4961703.41.82512070.26830527510.21.0773.4911953.41.82714890.19337033013.81.0775.44911203.41.82817620.1
3、5343037517.41.0775.44911503.41.93020800.12449042621.71.0765.4411853.423224530.099156048026.71.2517.5912403.42.13431000.075466555534.61.257.58313003.42.23637230.060176563043.11.2567.5614003.42.34047280.04789072557.41.2457.553导体标称截面绝缘厚度护套厚度电缆近似外径电缆近似重量20导体电缆载流量短路电流直流电阻在空气中直埋土壤中导 体屏蔽层铜带铜丝mm 2mmmmmmkg/k
4、m/kmAAKAKAKA3253.42.34321320.7271201253.692.958-3353.42.34524910.5241401555.152.958-3503.42.44830910.3871651807.312.958-3703.42.65238840.26821022010.22.958-3953.42.75647780.19335526513.82.958-31203.42.85955950.15329030017.42.958-31503.42.96367320.12433034021.72.958-31853.436679540.099137538026.72.958-32403.43.27279290.075443543534.63.301-33003.43.377118550.060149548543.1