1、目录一: 前言二: 文字说明部分(1) 所址的选择 (2) 主变压器的选择 (3) 电气主接线选择 (4) 断路器及隔离开关的选择 (5) 互感器的选择(6) 导体的选择(7)补偿装置的选择(8)保护设立(9)所用变的选择三:计算说明部分(1) 主变压器的选择(2) 短路电流计算(3) 断路器及隔离开关的选择(4) 导体的选择(5) 互感器的选择(6) 补偿装置的选择(7) 保护设立(8) 设备清单四:谢辞附录1:1)变电站主接线图 2)总平面布置图 3)间隔断面图 4)继电保护配置图 5)防雷接地保护配置图 6)10KV屋内配置图前言:ABSTRACT:In the renovation o
2、f urban power network the difficulty caused by insufficient land for building and dense population is always met in the construction of urban substation. In order to simplify the writing of urban substation, in this paper three wiring modes are put forward, i.e., the wiring for line and transformer
3、sets, the wiring for internal bridge and the wiring for single busbar. To solve the difficulties in the building up of urban substations, a practical experience of building up substation near the park at the center of the city is presented, in which three ways such as indoor wiring and installation,
4、 multi-layer arrangement and comprehensive utilization of multifunction buildings are applied. KEYWORDS: urban network construction; substation; urban network renovation摘要: 针对城网改造工作中,由于城市人口密集,土地资源紧张给市区变电所建设带来的困难,提出了“线路变压器组接线”、“内桥接线”和“单母线接线”3种接线方式,使变电所接线简朴化。文中介绍了采用室内化、多层布置和综合运用多功能建筑等方法,在公园附近建设城市中心变电所
5、的实践,解决了市区变电所建设的诸多难题,同时对该变所的无人值班综合自动化系统作了简朴介绍。关键词:城网建设;变电所;城网改造110KV变电所电气设计说明所址选择:一方面考虑变电所所址的标高,历史上有无被洪水浸淹历史;进出线走廊应便于架空线路的引入和引出,尽量少占地并考虑发展余地;另一方面列出变电所所在地的气象条件:年均最高、最低气温、最大风速、覆冰厚度、地震强度、年平均雷暴日、污秽等级,把这些作为设计的技术条件。主变压器的选择:变压器台数和容量的选择直接影响主接线的形式和配电装置的结构。它的拟定除依据传递容量基本原始资料外,还应依据电力系统5-2023的发展规划、输送功率大小、馈线回路数、电压
6、等级以及接入系统的紧密限度等因素,进行综合分析和合理选择。选择主变压器型式时,应考虑以下问题:相数、绕组数与结构、 绕组接线组别(在电厂和变电站中一般都选用YN,d11常规接线)、调压方式、 冷却方式。 由于本变电所具有三种电压等级110KV、35KV、10KV,各侧的功率均达成变压器额定容量的15%以上,低压侧需装设无功补偿,所以主变压器采用三绕组变压器。为保证供电质量、减少线路的损耗此变压器采用的是有载调压方式,在运营中可改变分接头开关的位置,并且调节范围大。由于本地区的自然地理环境的特点,故冷却方式采用自然风冷却。 为保证供电的可靠性,该变电所装设两台主变压器。当系统处在最大运营方式时两
7、台变压器同时投入使用,最小运营方式或检修时只投入一台变压器且能满足供电规定。 所以选择的变压器为2SFSZL7-31500/110型变压器。变电站电气主接线: 变电站主接线的设计规定,根据变电站在电力系统中的地位、负荷性质、出线回路数等条件和具体情况拟定。通常变电站主接线的高压侧,应尽也许采用短路器数目教少的接线,以节省投资,随出线数目的不同,可采用桥形、单母线、双母线及角形接线等。假如变电站电压为超高压等级,又是重要的枢纽变电站,宜采用双母线带旁母接线或采用一台半断路器接线。变电站的低压侧常采用单母分段接线或双母线接线,以便于扩建。610KV馈线应选轻型断路器,如SN10型少油断路器或ZN1
8、3型真空断路器;若不能满足开断电流及动稳定和热稳定规定期,应采用限流措施。在变电站中最简朴的限制短路电流的方法,是使变压器低压侧分列运营;若分列运营仍不能满足规定,则可装设分列电抗器,一般尽也许不装限流效果较小的母线电抗器。故综合从以下几个方面考虑:1 断路器检修时,是否影响连续供电;2 线路能否满足,类负荷对供电的规定;3大型机组忽然停电对电力系统稳定运营的影响与产生的后果等因素。主接线方案的拟定:对本变电所原始材料进行分析,结合对电气主接线的可靠性、灵活性及经济性等基本规定,综合考虑。在满足技术、经济政策的前提下,力争使其技术先进,供电可靠,经济合理的主接线方案。此主接线还应具有足够的灵活
9、性,能适应各种运营方式的变化,且在检修、事故等特殊状态下操作方便、调度灵活、检修安全、扩建发展方便。故拟定的方案如下:方案:110KV侧采用内桥接线,35KV采用单母分段,10KV单母接线。 方案:110KV侧采用单母分段,35KV采用单母分段带旁母,10KV采用单母分段。 由以上两个方案比较可知方案的110KV母线侧若增长负荷时不便于扩建,35KV、10KV出线的某一回路出现故障时有也许使整个线路停止送电,所以很难保证供电的可靠性、不便于扩建检修,故不采用。方案的110KV母线侧便于扩建,35KV线路故障、检修、切除或投入时,不影响其余回路工作,便于倒闸操作,10KV侧某一线路出现故障时不至
10、于使整个母线停电,满足供电可靠、操作灵活、扩建方便等特点,所以采用方案,主接线图如图 所示。高压断路器和隔离开关的选择:1 断路器种类和型式的选择按照断路器采用的灭弧介质可分为油断路器、压缩空气断路器、SF6断路器、真空断路器等。 2 额定电压和电流选择,式中 、分别为电气设备和电网的额定电压,KV、分别为电气设备的额定电流和电网的最大负荷电流,A。3 开断电流选择 高压断路器的额定开断电流,不应小于实际开断瞬间的短路电流周期分量,即4 短路关合电流的选择 为了保证断路器在关合短路电流时间的安全,断路器的额定关合电流不应小于短路电流最大冲击值。5 断路热稳定和动稳定的校验 校验式,隔离开关的选
11、择:隔离开关也是发电厂和变电所中常用的开关电器。它需与断路器配套使用。但隔离开关无灭弧装置,不能用来接通和切断负荷电流和短路电流。隔离开关与断路器相比,额定电压、额定电流的选择及短路动、热稳定的项目相同。但由于隔离开关不用来接通和切断短路电流,故无需进行开断电流和短路关合电流的校验。互感器的选择: 互感器是电力系统中测量仪表、继电保护等一次设备获取电气一次回路信息的传感器。互感器将高电压、大电流按比例变成低电压(100、100/)和小电流(5、1A)。电流互感器的二次侧绝对不可以开路。电压互感器的二次侧绝对不可以短路1 种类和型式的选择 选择电流互感器时,应根据安装地点(如屋内、屋外)和安装方
12、式(如穿墙式、支持式、装入式)选择其型式。当一次电流较小时,宜优先采用一次绕组多匝式,弱电二次额定电流尽量采用1A,强电采用5A。2 一次回路额定电压和电流的选择, 式中 、分别为电气设备和电网的额定电压,KV、分别为电气设备的额定电流和电网的最大负荷电3准确级和额定容量的选择 互感器所选定准确级所规定的额定容量应大雨等于二次册所接负荷,即4 热稳定和动稳定的校验,为电流互感器1S通过的热稳定电流,为电流互感器的动稳定电流。裸导体的选择: 导体截面可按照长期发热允许电流或经济电流密度选择。对年负荷运用小时数大(通常指5000h),传输容量大,长度在20m以上的导体,如发电机、变压器的连接导体其
13、截面一般按经济电流密度选择。而配电装置的汇流母线通常在正常运营方式下,传输容量大,可按长期允许电流来选择。1 按导体长期发热允许电流选择k2 按经济电流密度选择=3 电晕电压校验4 热稳定动稳定校验=按电压损失规定选择导线截面(一般用于10KV以下):为保证供电质量,导线上的电压损失应低于最大允许值,通常不超过5%。因此,对于输电距离较长或负荷电流较大的线路,必须按允许电压损失来选择或校验导线截面。设线路允许电压损失为Ual%即 P(rl)+Q(xl)/102Ual%补偿装置的选择:电力系统的无功功率平衡是系统电压质量的主线保证。在电力系统中,整个系统的自然无功负荷总大于原有的无功电源,因此必
14、须进行无功补偿。通常情况下110KV的变电所是在35KV母线和10KV母线上进行无功补偿,本变电所是在10KV母线上并联电容器和可调节的并联电抗器为重要的无功补偿(并联电容器和并联电抗器是电力系统无功补偿的重要常用设备,予优先采用),既将功率因数由0.8提高至0.92,合理的无功补偿和有效的电压控制,不仅可以提高电力系统运营的稳定性、安全性和经济性,故所选的电容器型号为10-1500/50。避雷装置的选择:避雷针:单根接地电阻不大雨10,应布置单根垂直接地体,P=50/m ,L=2.5m,d=0.05m的钢管,由60*6的扁钢连接,埋入地下3m处。接地电阻Rc=22.9。避雷器:对于本变电所来
15、说,采用氧化锌避雷器,110KV线路侧一般不装设避雷器,主变压器低压侧的一相上宜装设一台Y5W-12.7/42型避雷器,35KV出线侧装设Y10W5-42/142型避雷器。接地网:变电所内必须安装闭合的接地网,并装设必需的均压带,接地网采用水平接地为主,辅以垂直的封闭复合式接地网。主接地网电阻R4;避雷针设独立接地体,它于主接地网地中距离T5m,其接地电阻R10。接地网有均压、减少接触电势和跨步电压的作用,又有散流作用。在防雷接地装置中,可采用垂直接地体作为避雷针、避雷线和避雷器附近加强集中接地和散泄电流的作用。变电所不管采用何种接地体应敷设水平接地体为主的人工接地网。 人工接地网的外缘应闭合
16、,外缘的各角应做成圆弧行,圆弧半径不宜小于均牙带间距的一半,接地网内敷设水平的均压带。接地网一般采用0.6m0.8m,在冻土地区应敷设在冻土层以下。 均压带经常有人出入的走道应铺设沥青面(采用高电阻率的路面结构层),接地装置敷设成环形,目的是防止应接地网流过中性点的不平衡电流在雨后地面积水成泥污时,接地装置附近的跨步电压引起行人和牲畜的触电事故。 此接地网水平接地体采用的是60*6的扁钢敷于地下0.8m处,垂直接地体为50 ,L=2.5m的圆钢,自地下0.8m处与水平接地体焊接,接地体引上线采用25*4的扁钢与设备焊接。接地网的工频电阻R0.5。 敷设在大气和土壤中有腐蚀的接地体和接地引下线,
17、需采用一定的防腐措施(热镀锌,镀锡)。所用变的设立:为保证重要变电所的安全用电,所以需装设两台所用变,以备用。为了保证供电的可靠性应在35KV和10KV母线上各装设一台变压器。若只在10KV母线上引接所用电源,由于低压线路故障率较高,所以不能保证变电所的不间断供电。故所用变采用的型号是S6-50/10、S6-50/35。接线图如下所示: 变电所的自动化控制:本变电所采用综合自动化设备,远动信息按四遥配置。1. 遥测35KV线路有功功率、电流和电能;10KV 线路有功功率、电流和电能;10KV电容器电流和电能;110KV、35KV、10KV各段母线电压;主变压器高、中、低侧有功功率、电流和电能;
18、所用电和直流系统母线电压;2. 遥信110KV、35KV、10KV线路断路器、隔离开关、PT隔离刀闸位置;主变三侧断路器、隔离开关、中性点接地位置;主变瓦斯动作信号;差动保护动作信号;复合电压闭锁过电流保护动作信号;低频减载动作信号;35KV、10KV系统接地信号、保护动作信号;断路器控制回路断线总信号;变压器油温过高信号;主变压器轻瓦斯动作信号;变压器油温过低总信号;微机控制系统交流电源消失信号;微机控制系统下行通道信号;直流系统绝缘监测信号;遥控转为本地控制信号;3. 遥调变压器档位调节4. 遥控110KV及以下断路器分合、预告信号复归。电缆设施及防水:该变电所配电设有电缆沟,电缆沟沿主建
19、筑物至主变区配合装置。通过电缆沟把控制及动力电缆引接到控制室及动力屏,在电缆沟进建筑物时,加装穿墙孔板,待电缆施工后进行封墙,防止火的蔓延和小动物进入。为防止干扰,二次电缆采用屏蔽电缆。变压器事故排油系统:变电所设有两台变压器,当主变压器发生事故时,要排出变压器油。因此,考虑设一座变压器排油井,用DN150铸铁管排入事故贮油井内,不考虑回收运用,排油井设在所区内空地。消防系统: 变电所一般为多油、电引起火灾,危险性较大,宜选用化学和泡末剂灭火,且变压器旁可设立消防砂。保护配置:主变保护部分:采用微机保护装置A. 差动保护 防止变压器绕组和引出线相间短路,直接接地系统侧和引出线的单相接地短路及绕
20、组见的短路。B. 瓦斯保护 防止变压器油箱内部或断线故障及油面减少。C. 零序电流保护、零序电压保护 防止直接接地系统中变压器外部接地短路并作为瓦斯保护和差动保护的后备。D. 防止变压器过励磁。E. 过电流保护(或阻抗保护) 防止变压器外部相间短路并作为瓦斯保护和差动保护的后备。F. 过负荷保护 防止变压器对称过负荷。G. 反映变压器油温及油箱内压力升高和冷却系统故障的相应保护。110KV、35KV线路保护部分:A. 距离保护B. 零序过电流保护C. 自动重合闸D. 过电压保护 在变电所周边装设独立避雷针,为防止直击雷和雷电波的危害,在35kV和10kV出线均安装金属氧化物避雷器;变压器安装金
21、属氧化物避雷器;10kV母线也用一组金属氧化物避雷器进行过压保护。10KV线路保护:1、10kV线路保护:采用微机保护装置,实现电流速断及过流保护、实现三相一次重合闸。 2、10kV电容器保护:采用微机保护装置,实现电流过流保护、过压、低压保护。 3、10kV母线装设小电流接地选线装置,发送有选择性的单相接地遥信。 计算部分变压器的选择:负荷计算:最大负荷时:1. 35KV出线=tan=9tan(arccos0.8)=6.75Mvar=tan=12tan(arccos0.8)=9Mvar=tan=8tan(arccos0.8)=6Mvar2. 10KV出线=tan=1tan(arccos0.8
22、)=0.75Mvar=tan=1tan(arccos0.8)=0.75Mvar=tan=0.8tan(arccos0.8)=0.6Mvar=tan=0.9tan(arccos0.8)=0.675Mvar=tan=0.6tan(arccos0.8)=0.45Mvar=tan=0.8tan(arccos0.8)=0.6Mvar于是母线侧的总负荷为 =+ = 0.85(9+12+8)+0.8(1+1+0.8+0.9+0.6+0.8) =24.65+4.08 =28.73MW=+ = 0.85(6.75+9+6)+0.8(0.752+0.6+0.675+0.45+0.6) =14.4875+3.06
23、= 21.5475Mvar最小负荷时:1.35KV出线=tan=7tan(arccos0.8)=5.25Mvar=tan=8tan(arccos0.8)=6Mvar=tan=6tan(arccos0.8)=4.5Mvar2.10KV出线=tan=0.5tan(arccos0.8)=0.375Mvar=tan=0.7tan(arccos0.8)=0.525Mvar=tan=0.3tan(arccos0.8)=0.225Mvar=tan=0.5tan(arccos0.8)=0.375Mvar=tan=0.3tan(arccos0.8)=0.15Mvar=tan=0.4tan(arccos0.8)=
24、0.3Mvar于是母线侧的总负荷为 =+ = 0.85(7+8+6)+0.8(0.5+0.7+0.3+0.5+0.2+0.4) =17.85+2.08 =19.93MW=+ = 0.85(5.25+6+4.5)+0.8(0.375+0.525+0.225+0.375+0.3) =13.3875+1.56 = 14.9425Mvar则系统的计算负荷为:最大运营方式下:=35.9125MVA最小运营方式下:=24.9125MVA若待建变电所考虑15%的负荷发展余地,则=42.25 MVA=29.3 MVA考虑到变电所的安全运营,故需选用两台同样的变压器,且在系统最大运营方式下两台变压器并列运营。系
25、统最小运营方式下只起用一台变压器。综上考虑,选用两台绕组无励磁的调压变压器,其参数如下所示:型 号:SFSZL7-31500/110额定容量:31500 KVA额定电压:11022.5% 3522.5% 6.3空 损:46KW负 损:175 KW阻抗电压%:高-中10.5 高-低17-18 中-低6.5联结组号: 所用电负荷记录如下:设备名称容量(W)空调照明、电热取暖附属建筑取暖主变风扇载波通讯检修用电微机用电合计1000080001000024006006000202339000考虑各母线上的电压平衡,所用电取自于10KV母线,由以上计算数据可选用S6-50/10型和S6-50/35型变压
26、器。其参数如下所示:额定电压:10/0.4 额定电压:35/0.4额定电压:10/0.4 额定电压:10/0.4连接组构号Y. 连接组构号Y.短路电流计算:取=100MWA,=.变压器各绕组电抗标幺值计算如下:各绕组的短路电压分别为:%=1/2%+ %-% =1/2(10.5+17.5-6.5)=10.75%=1/2%+ %-% =1/2(10.5+6.5-17.5)=-0.25%=1/2%+ %-% =1/2(17.5+6.5-10.5)=6.75各绕组的电抗标幺值计算如下:=(%/100)(/)=(10.75/100)(100/31.5)=0.34=(%/100)(/)=(-0.25/10
27、0)(100/31.5)=-0.008=(%/100)(/)=(6.75/100)(100/31.5)=0.214变压器的等值网络如图1-1所示:当系统母线高压侧的最大三相短路容量为2023MVA时,短路电流的计算系统的等值网络如图1-2所示:其中X1=/2=0.34/2=0.17 X2=/2=-0.008/2=-0.004 X3=/2=0.214/2=0.107 Xd=/=100/2023=0.051. 当f1点短路时 =/()=100/(37)=1.56KA短路电流 =1/(X1+X2+Xd)=1/(0.17-0.004+0.05)=4.63短路电流的有名值 =4.631.56=7.22K
28、A冲击电流 =1.8=1.87.22=18.385KA短路容量 =4.63100=463MVA 2 当f2点短路时 =/()=100/(10.5)=5.5KA短路电流 =1/(X1+X3+Xd)=1/(0.17+0.107+0.05)=3.058短路电流的有名值 =5.53.058=16.82KA冲击电流 =1.8=1.816.82=46.82KA短路容量 =3.058100=305.8MVA3 当f3点短路时 =/()=100/(115)=0.502KA短路电流 =/()=2023/(1150.502)=20短路电流的有名值 =200.502=10.04KA冲击电流 =1.8=1.810.0
29、4=25.56KA断路器及隔离开关:A. 变压器110KV侧断路器及隔离开关变压器的最大工作电流 =(1.05)/()=1.0531500/110=173.6A根据线路的电压及最大工作电流及断路器在屋外的规定,查表可选择LW14-110型断路器。短路时间: =0.2+0.06+0.03=0.29S周期分量的热效应:=/12(+10+)=0.29/12(+10+)=29.23.S非周期分量的热效应:1时,T=0.05 =T=0.05=5.04.S短路电流的热效应:=+=29.23+5.04=34.27.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据LW14-110型断路器GW4
30、-110D/1000-80型隔离开关 110KV 173.6A 10.04KA 25.56KA34.27.S 25.56KA 110KV 2023A 31.5KA 80KAt=4800.S 80KA 110KV 1000At=2311.5.S 80KA由以上数据比较可知LW14-110型断路器和GW4-110D/1000-80型隔离开关均可以吗组规定。B. 变压器35KV侧断路器及隔离开关变压器的最大工作电流 =(1.05)/()=1.0531500/35=545.6A根据线路的电压及最大工作电流及断路器在屋外的规定,查表可选择LW8-35型断路器。短路时间: =0.7+0.06+0.03=0
31、.79S周期分量的热效应:=/12(+10+)=0.79/12(+10+)=41.18.S非周期分量的热效应:1时,T=0.05 =T=0.05=2.61.S短路电流的热效应:=+=41.18+2.61=43.79.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据LW8-35型断路器。GW5-35G/600-72型隔离开关 35KV 545.6A 7.22KA 18.385KA43.79.S 18.385KA 35KV 1600A 25KA 63KAt=2500.S 63KA 35KV 600At=1024.S 72KA由以上数据比较可知LW8-35型断路器和GW5-35G/6
32、00-72型隔离开关均可以吗组规定。C. 变压器10KV侧断路器及隔离开关变压器的最大工作电流 =(1.05)/()=1.0531500/10=1909.6A根据线路的电压及最大工作电流及断路器在屋内的规定,查表可选择ZN-10/2023-40型断路器。短路时间: =0.7+0.06+0.05=0.81S周期分量的热效应:=/12(+10+)=0.81/12(+10+)=229.2.S非周期分量的热效应:1时,T=0.05 =T=0.05=14.15.S短路电流的热效应:=+=229.2+14.15=243.35.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据ZN-10/20
33、23-40型断路器GN2-10/2023-85型隔离开关 10KV 1909.6A 16.82KA 42.82KA243.35.S 42.82KA 10KV 2023A 40KA 100KAt=3200.S 100KA 10KV 2023At=1300.S 85KA由以上数据比较可知ZN-10/2023-40型断路器和GN2-10/2023-85型隔离开关均可以吗组规定。D. 35KV出线侧断路器及隔离开关线路的最大工作电流 =(1.05)/(COS)=1.05121000/350.8=259.8A根据线路的电压及最大工作电流及断路器在屋外的规定,查表可选择LW8-35/1600型断路器。短路
34、时间: =0.7+0.03+0.03=0.0.76S周期分量的热效应:=/12(+10+)=0.76/12(+10+)=39.62.S非周期分量的热效应:1时,T=0.05 =T=0.05=2.61.S短路电流的热效应:=+=39.62+2.61=42.23.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据LW8-35/1600型断路器GW5-35G/600-72型隔离开关 35KV 259.8A 7.22KA 18.385KA42.23.S 18.385KA 35KV 1600A 25KA 63KAt=2500.S 63KA 35KV 600At=1024.S 72KA由以上
35、数据比较可知LW8-35/1600型断路器和GW5-35G/600-72型隔离开关均可以吗组规定。E. 线路10KV出线侧断路器及隔离开关线路的最大工作电流 =(1.05)/(COS)=1.0511000/100.8=75.78A根据线路的电压及最大工作电流及断路器在屋内的规定,查表可选择ZN4-10/1250-20型断路器。短路时间: =0.7+0.06+0.05=0.0.81S周期分量的热效应:=/12(+10+)=0.81/12(+10+)=229.2.S非周期分量的热效应:1时,T=0.05 =T=0.05=14.15.S短路电流的热效应:=+=229.2+14.15=243.35.S
36、断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据ZN4-10/1250-20型断路器GN6-10T/600-52型隔离开关 10KV 75.78A 16.82KA 42.82KA243.4.S 42.82KA 10KV 1250A 20KA 50KAt=1600.S 50KA 10KV 600At=1600.S 52KA由以上数据比较可知ZN4-10/1250-20型断路器和GN6-10T/600-52型隔离开关关均可以吗组规定。F. 110KV侧母联断路器及隔离开关母线的最大工作电流 =2(1.05)/()=2*1.0531500/110=347.2A根据线路的电压及最大工作电
37、流及断路器在屋外的规定,查表可选择LW14-110型断路器。短路时间: =0.2+0.06+0.03=0.29S周期分量的热效应:=/12(+10+)=0.29/12(+10+)=29.23.S非周期分量的热效应:1时,T=0.05 =T=0.05=5.04.S短路电流的热效应:=+=29.23+5.04=34.27.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据LW14-110型断路器GW4-110D/1000-80型隔离开关 110KV 347.2A 10.04KA 25.56KA34.27.S 25.56KA 110KV 2023A 31.5KA 80KAt=4800.
38、S 80KA 110KV 1000At=2311.5.S 80KA由以上数据比较可知LW14-110型断路器和GW4-110D/1000-80型隔离开关均可以吗组规定。G. 35KV母联断路器及隔离开关线路的最大工作电流 =3*(1.05)/(COS)=3*1.05121000/350.8=779.4A根据线路的电压及最大工作电流及断路器在屋外的规定,查表可选择LW8-35/1600型断路器。短路时间: =0.7+0.03+0.03=0.0.76S周期分量的热效应:=/12(+10+)=0.76/12(+10+)=39.62.S非周期分量的热效应:1时,T=0.05 =T=0.05=2.61.
39、S短路电流的热效应:=+=39.62+2.61=42.23.S断路器及隔离开关的相关数据并与计算值相比较,如下所示:计算数据LW8-35/1600型断路器GW5-35G/1600-72型隔离开关 35KV 779.4A 7.22KA 18.385KA42.23.S 18.385KA 35KV 1600A 25KA 63KAt=2500.S 63KA 35KV 1600At=1024.S 72KA由以上数据比较可知LW8-35/1600型断路器和GW5-35G/600-72型隔离开关均可以吗组规定。导线截面的选择:1) 110KV侧母线的选择按经济电流密度选择导线的截面,由于=5000h/年,查
40、表可得J=1.07A/。 变压器110KV母线的最大工作电流=2173.6=347.2A所以S=/J=347.2/1.07=309.03故 可选择型号为LGJ-400/20的导线,其载流量为800A热稳定校验:=。+(al-。)=35+(70-35)=42 由此查表胡的C=98.4则 =/C=/98.4=59.5400 满足导线的最小截面的规定。 2) 35KV侧母线的选择按经济电流密度选择导线的截面,由于=5000h/年,查表可得J=1.07A/。 变压器35KV母线的最大工作电流=/COS=597.97A所以S=/J=597.97/1.07=558.85故 可选择型号为LGJ-630/45的导线,其载流量为712A热稳定校验:=。+(al-。)=35+(70-35)=57 由此查表胡的C=92.8则 =/C=/92.8=70.03630 满足导线的最小截面的规定。3) 10KV母线的选择按经济电流密度选择导线的截面,由于=5000h/年,查表可得J=1.07A/。 变压器10KV母线的最大工作电流=/COS=368A所以S=/J=368/1.07=344故 可选择型号为LMY-606的矩形铝导体,其载流量为632A热稳定校验:=。+(al-。)=35+(70-35)=47 由此查表胡的C=97.6则 =/C=/97.6=66.5630