1、 Quality and environmental Management Manual Part 2 质量和环境管理手册 第2部分Section 章节: PI Ver. No.版本号: Page 页码: 1 of 7 Prepared by 制订:Guo, Lianwei Building&Facility maintenance operation procedure厂房设施维护作业程序1 Purpose and Scope目的和适用范围To establish a set of procedures to ensure a standard work instruction onbuil
2、ding maintaining and repairing facility related equipment. To ensure reliableprocedure on maintaining and repairing facility related equipment. It is just for allVosslon s building and facilities in Kunshuan factory.为确保建筑物及公用设备实施得以可靠性维护及维修,建立一套程序来规范设施维护的作业过程,仅适用于福斯罗昆山工厂的所有建物及各类设施。2 Responsible proce
3、sses过程负责人2.1 The Facility Maintenance section head 设施维护部门主管职责2.1.1 Set up a preventive maintenance plan for all buildings and facilities .建立针对所有建物及设施的预防性维护计划2.1.2 Arrange annual maintenance of major facility equipment.安排针对主要厂务设施的年度维护作业2.1.3 Supervise all facility related activities.督导所有的厂务相关活动2.1.4
4、Provide technical support to facility equipment repairs andmaintenance.提供对厂务设备维修及维护的技术支持2.1.5 Ensure all facility related activities follow safety and enviromentrequements.确保全部相关厂务作业活动符合安全及环保要求。2.2 Facility Maintenance Personnel 设施维护人员职责Carry out factory buildings and facilities equipment preventive
5、 maintenanceand repair activites. Inspection of facility related equipment实施工厂建筑及厂务设施的维护及维修活动,执行相关设施的日常检查。3 Procedure 工作程序3.1 Buildings and infrastructures 建筑物及基础设施定期性维护 Regular inspection and maintenance : 质量和环境管理手册第2部分3.1.1 每个季度查检建筑物的墙面,地板,屋顶,顶板,门窗,建物设施,若有明显损坏需及时修复;Quarterly inspection for buildin
6、gs walls, floors, ceilings,rooves,doors&windows etc.Restore it on time if any evident damage.3.1.2 每个季度检查及清理屋面垃圾,保持屋面排水顺畅。对外露金属构件进行必要的除锈并防腐处理;Quarterly inspection for cleaning garbages on roof, keeping the smoothdrainage. necessary treatment of cutting rust and anticorrosion toexposed metal structur
7、e .3.1.3 定期检查钢构厂房屋面,气楼及酸洗车间被腐蚀的情形,根据实际情况采取必要的维护措施;To check the status of the roof,cleanstory,pickling shop of steelstructure building. Take necessary measures to it based on acturalsituation.经常性维护Daily maintenance :3.1.4 办公区域公共走道,会议室等公共场所,保持墙面整洁及设施完好;各类门窗在使用过程中发现的不良问题需要及时处理;To keep the public walls
8、such as walkway,meeting room be clean andin good situation. To deal with the unhealthy facility problem while thedoors and windows are being used.3.1.5 厂区路面及车间环氧树脂地板,及时修复各种原因造成的初期损坏,避免更大的损坏发生;To inspect all epoxy floors in factory area and workshop frequently,recover all original damage caused by an
9、y reason timely.3.1.6 经常性检查单体建物的功能性及结构安全性检查,及时解决及消除建物的安全隐患routine check of function and structure for each singular building, settleand remove all potential safety problem.3.2 Lighting 照明周期性维护Regular maintenance:3.2.1 每个季度全面检查厂区照明,车间照明及各类公共区域照明,对于损坏的灯具及不良电气配件整体性更换及维护;Quarterly overall inspection for
10、 whole plant lighting and public lighting,repair and change all damaged lamps and defective parts timely.3.2.2 每年全面检查一次照明供电线路的状况,对各类照明电气节点进行检查及紧固;Once anual inspection for the power supply cable of lighting, Confirmand fasten all the electric connecters and joints.3.2.3 更换性能老化且已严重影响供电安全的照明线路,确保用电安全;
11、Replace the lighting wires which is aged and affecting the power safety.Ensure safety of using.经常性维护Daily maintenance: 质量和环境管理手册第2部分3.2.4 对于办公区域的照明需保持良好的工作状态,发现损坏的灯管或灯泡,立即更换;Keeping the good satus for lighting in office area, chage the damagedlamps or bulbs immediately.3.2.5 对于公共区域照明要兼并考虑节能及保障照度的要求,
12、尽可能使用光控开关管理公共部分照明。Energy saving and brightness of public lighting should be considered. Itis better to try to manage public lighting by the twilight sensor.3.3 Air conditioning and ventilating system 空调及通风系统3.3.1 中央空调每年根据保养手册的要求,更换冷却润滑油及过滤器等;Yearly change the cutting oil and filters for central air
13、conditioner basedon operation and maintenance anual.3.3.2 每两年对中央空调水系统进行一次清洗及水处理;检查所有管道设施齐全有效;Once pipes cleanliness and water treatment for central air conditionersystem every two year, making sure all pipes and accessaries arecomplete and effective.3.3.3 在空调季节,每季度清洗一次室内所有风机盘管的回风滤网;Quarterly once cl
14、eanliness for filter screens of all inside fan coil units inthe seasons which need air conditioning.3.3.4 对于分体式空调在空调季节每月清洗一次内机滤网;Monthly once cleanliness for filter screens of all independent airconditioners.3.3.5 每个季度例行检查并维护建筑通风系统,保持室内健康的空气环境。Quarterly regular inspection and maintenance for buildin
15、gs ventilatorsystem. Keep health enviroment inside.3.4 Water supply and drainage system 给排水系统3.4.1 每个季度检查屋面排水口有无堵塞,管道检查口有无松脱;Quarterly inspection whether all drainage outlets on roof are blockedand pipeline check mouthes are loose.3.4.2 如有发现管路跑冒滴漏的情形及时处理,避免对他物造成破坏;Deal with all situation about water
16、 leakage immediately anywhere, Tryto avoid damage for others.3.4.3 及时通知环卫部门每个季度清理一次厂区化粪池;Inform enviroment and health station in time to clean all the digestiontanks every quarter.3.4.5 保持雨污水分流。禁止任何地下管路改造导致雨污水混排。Remain rain pipes system and waste water system separately. It isforbidden to mixed rain
17、 water and sewage water because of any pipesreconstruction. 质量和环境管理手册第2部分3.5 Fire fighting system 消防系统3.5.1 每年与消防维保单位签订年度维保协议,维保单位须根据国家规范及合约约定执行各项维保工作;To sign up agreement with fire-fighting service company every year.And supplier must carry out all maintenance contents based onChinas criteria and a
18、greement signed.3.5.2 每月检查所有消防栓及灭火器,保持现场灭火设施处于良好的状态;Yearly inspection for all hydrants and extinguishers in the factory.Make sure good status of all fire-fighting equipments anytime.3.5.3 发现消防报警系统或消防栓灭火系统的故障须及时处理,消除安全隐患;Deal with all failures and faults of fire alarm system and hydrantsystem sooner.
19、 Clear up all potential safety problem.3.5.4 重点场所的报警装置例如锅炉房,液化气站的燃气报警系统若有必要的需要委外检测及校验;Some alarm devices at key location like the gas alarm system of boilerroom, LPG station should be tested and calibrated by outsidecompany.3.6 Cranes 起重机3.6.1 与专业公司签订行车维保协议,确保维保公司按照检测规程及合约规定执行定期性维保工作;Sign up the mai
20、ntenance agreement with professional supplier toensure supplier provide regular maintenance service for all cranesaccording to inspection standard.3.6.2 备有适当的替换备件,避免生产过程中因配件损坏导致停产事故To prepare necessary spare parts to prevent production shut downbecause of damaged components.3.7 Kitchens epuipment 厨房
21、设备3.7.1 厨房主管经常性检查厨房设备的完好状况,发现设备故障及时通知维修人员处理;Kitchens supervisor shoud often inspect all equipments. If any faultshappens, inform the related person.3.7.2 燃气具使用完毕后需要及时关闭燃气,发生设备漏气及时停用设备,待修复后方能再投入使用;Gas cooker should be turned off after work. Failed equipment leakinggas shoud be out of service right aw
22、ay. Then use it again until its wellrepaired.3.7.3 厨房下水道的厨余垃圾需要及时清理,防止排水管道堵塞;To dispose the garbage in the sewage ditch of kitchen. Prevent fromthe sewage pipes not to block. 质量和环境管理手册第2部分3.7.4 室外隔油池需要经常性清理以防止油逅沉积粘附于管道。It is necessary to often clean the outside oil separation tank to preventfrom the
23、 grease catch the pipes inwall.3.8 Boiler room 锅炉房3.7.1 锅炉操作工需严格按照操作手册管理锅炉设备,值班期间每两个小时巡查一次锅炉运行状况并填写值班记录;Boiler workers should operate boilers in strict accordfance withoperation annual, Go to patrol once every two hours for mornitoringboiler running and write down the record on duty book.3.7.2 检查人员需
24、特别注意软化水的存量,避免锅炉发生干烧;The duty person should particularly pay attention to the stock of waterin the supplementary tank. Avoid the boilers to be heated with out.3.7.3 锅炉的温度表,压力计及安全阀等安全阀件至少每年委外校验一次;The thermometers, pressure meters of boiler at least are must becalibrated every year.3.7.4 每天巡回检查天然气供应管道有
25、无漏气等异常情况发生;Patrol inspection for natural gas leakage everyday is required.3.7.5 经常性检查管道有无泄漏水,蒸汽等,目视管道是否严重腐蚀,发生任何异常及时报告设备主管;Frequently inspect the water and steam leakage, observe the rustyposobility of pipes with visual way. If any abnormal matter happens,report the facility management early.3.7.6 与
26、专业维保单位签订天然气管道维保协议,每月进行一次全面检查,若有紧急状况发生,立即通知维保单位到场处理。To sigh up the maintenance agreement with professional supplier,onceoverall inspection by service supplier. If any serious accident happens,call service supplier immediately.3.9 Air compressor room 空压机房3.9.1 值班人员每班须至少巡查一次空压设备的运行状况,保证供气压力及空气干燥质量;及时排放
27、储气罐内积水并填写点检记录;Duty person must at least go to patrol for compressors running stateand fill datas on the inspection table. Drain out the warter in the airstorage tank. On its purpose is to insure the air pressure and quality ofdry.3.9.2 根据末端用气需求适当调节投入运行的设备数量,在保证供气量的前提下,节省电能;Properly adjust the quanti
28、ty of compressors which are keeping runningaccording to the requirement of terminals. Try to save electricity byproviding enough air capacity.Section章节: PI 02-01 Ver. No.版本号:3/18.11.09 Quality and Environmental Management Manual Part 2 Page页码: 6 of 7 质量和环境管理手册 第2部分 3.9.3 根据空压机运行时间及时更换耗材,保持空压机的运行效率;
29、Replace the consumable parts in accordance with compressors runtime. Remain the satisfied efficiency for compressors. 3.9.4 经常性检查内部管道是否有漏气或漏油现象,发现异常及时通知服务商 处理,供电问题通知生产电工处理; Regular inspection for gas and oil leakage of air pipes. Call service company for dealing with any abnormal expect the electric
30、al problem which is in charged by production electrician. 3.9.5 保持空压机房内的理想环境,较好的清洁度及符合设备运行条件的温 度,妥善处理替换下的废弃冷却油及耗材零件。 Remain the fitting surrounding in compressors room like well cleanliness and tempareture. To dopose the waste oil and consumable parts in a correct way. 3.9.6 各类安全阀及压力表必须不超过1年委外检测一次,确
31、定所有安全装置 工作在有效期内。 All safety valves and pressure meters must be calibrated by outside qualified organization every year. To idnetify all safty divices are all in period of validity. 3.10 LPG station 液化气站 3.10.1 值班人员除了巡检锅炉房及空压机房外,需要坚守液化气站值班岗 位,监控供气系统安全运行,严格按照各类设备操作手册操作设备; Duty person must stay the dut
32、y room at LPG station expect inspection in boiler room and compressors room. Constantly monitoring the running of LPG supply system.Operating all equipments in strict coordance with instructions or operation anuals. 3.10.2 值班人员至少每两个小时需巡查一遍所有气站工作设备,听声嗅味辨 别设备运行状态是否正常,并填入值班记录; Duty person must at least
33、 go to patrol for inspection of all equipments which are in running every two hours. Identify the running state with listening and smelling. At last fill the duty book. 3.10.3 与专业维保单位签订液化气管道维保协议,每月进行一次全面检查, 若有紧急状况发生,立即通知维保单位到场处理; To sigh up the maintenance agreement with professional supplier,once o
34、verall inspection by service supplier. If any serious accident happens, call service supplier immediately. 3.10.4 各类安全阀及压力表必须不超过1年委外检测一次,确定所有安全装置 工作在有效期内; All safety valves and pressure meters must be calibrated by outside qualified organization every year. To idnetify all safty divices are all in p
35、eriod of validity. 3.10.5 经常性检查管道有无燃气泄漏,管道及阀门外层是否严重腐蚀,消防 器材是否合格有效,每年对站内室外所有管道刷漆防腐一次。 Photocopying and distribution to third parties is not allowed! 禁止复印和转交第三方! Section章节: PI 02-01 Ver. No.版本号:3/18.11.09 Quality and Environmental Management Manual Part 2 Page页码: 7 of 7 质量和环境管理手册 第2部分 Regularly inspection for gas leakage, rusty surface of all pipes, firefightring equipments anywhere. To paint all outdoor pipes at LPG station every year. 4 Annex 附录 【厂务设施维护检查表Facility maintenance and inspection schedule】 Photocopying and distribution to third parties is not allowed! 禁止复印和转交第三方!