1、南京工程学院 Nanjing Institute Of Technology毕业设计英文资料翻译The Translation Of The English Material Of Graduation Design 学生姓名: 学 号 : Name: Number: 班 级: K暖通091 Class: K-Nuantong 091 所在学院: 康尼学院 College: Kangni College 专 业: 建筑环境与设备工程 Profession: Building Environment and Equipment Engineering 指引教师: Tutor: 02月 25日英文
2、:Thermal comfort in the future - Excellence and expectationP. Ole Fanger and Jrn ToftumInternational Centre for Indoor Environment and Energy Technical University of DenmarkAbstractThis paper predicts some trends foreseen in the new century as regards the indoor environment and thermal comfort. One
3、trend discussed is the search for excellence,upgrading present standards that aim merely at an “acceptable” condition with a substantial number of dissatisfied. An important element in this connection is individual thermal control. A second trend is to acknowledge that elevated air temperature and h
4、umidity have a strong negative impact on perceived air quality and ventilation requirements. Future thermal comfort and IAQ standards should include these relationships as a basis for design. The PMV model has been validated in the field in buildings with HVAC systems that were situated in cold,temp
5、erate and warm climates and were studied during both summer and winter. In non-air-conditioned buildings in warm climates occupants may sense the warmth as being less severe than the PMV predicts,due to low expectations. An extension of the PMV model that includes an expectancy factor is proposed fo
6、r use in non-air-conditioned buildings in warm climates. The extended PMV model agrees well with field studies in non-air-conditioned buildings of three continents.Keywords:PMV,Thermal sensation,Individual control,Air quality,AdaptationA Search for ExcellencePresent thermal comfort standards (CEN IS
7、O 7730,ASHRAE 55) acknowledge that there are considerable individual differences between peoples thermal sensation and their discomfort caused by local effects,i.e. by air movement. In a collective indoor climate,the standards prescribe a compromise that allows for a significant number of people fee
8、ling too warm or too cool. They also allow for air velocities that will be felt as a draught by a substantial percentage of the occupants.In the future this will in many cases be considered as insufficient. There will be a demand for systems that allow all persons in a space to feel comfortable. The
9、 obvious way to achieve this is to move from the collective climate to the individually controlled local climate. In offices,individual thermal control of each workplace will be common. The system should allow for individual control of the general thermal sensation without causing any draught or oth
10、er local discomfort.A search for excellence involves providing all persons in a space with the means to feel thermally comfortable without compromise.Thermal Comfort and IAQPresent standards treat thermal comfort and indoor air quality separately,indicating that they are independent of each other. R
11、ecent research documents that this is not true . The air temperature and humidity combined in the enthalpy have a strong impact on perceived air quality,and perceived air quality determines the required ventilation in ventilation standards. Research has shown that dry and cool air is perceived as be
12、ing fresh and pleasant while the same composition of air at an elevated temperature and humidity is perceived as stale and stuffy. During inhalation it is the convective and evaporative cooling of the mucous membrane in the nose that is essential for the fresh and pleasant sensation. Warm and humid
13、air is perceived as being stale and stuffy due to the lack of nasal cooling. This may be interpreted as a local warm discomfort in the nasal cavity. The PMV model is the basis for existing thermal comfort standards. It is quite flexible and allows for the determination of a wide range of air tempera
14、tures and humidities that result in thermal neutrality for the body as a whole. But the inhaled air would be perceived as being very different within this wide range of air temperatures and humidities. An example:light clothing and an elevated air velocity or cooled ceiling,an air temperature of 28C
15、 and a relative humidity of 60% may give PMV=0,but the air quality would be perceived as stale and stuffy. A simultaneous request for high perceived air quality would require an air temperature of 20-22C and a modest air humidity. Moderate air temperature and humidity decrease also SBS symptoms and
16、the ventilation requirement,thus saving energy during the heating season. And even with air-conditioning it may be beneficial and save energy during the cooling season.PMV model and the adaptive modelThe PMV model is based on extensive American and European experiments involving over a thousand subj
17、ects exposed to well-controlled environments. The studies showed that the thermal sensation is closely related to the thermal load on the effector mechanisms of the human thermoregulatory system. The PMV model predicts the thermal sensation as a function of activity,clothing and the four classical t
18、hermal environmental parameters. The advantage of this is that it is a flexible tool that includes all the major variables influencing thermal sensation. It quantifies the absolute and relative impact of these six factors and can therefore be used in indoor environments with widely differing HVAC sy
19、stems as well as for different activities and different clothing habits. The PMV model has been validated in climate chamber studies in Asia as well as in the field,most recently in ASHRAEs worldwide research in buildings with HVAC systems that were situated in cold,temperate and warm climates and w
20、ere studied during both summer and winter. The PMV is developed for steady-state conditions but it has been shown to apply with good approximation at the relatively slow fluctuations of the environmental parameters typically occurring indoors. Immediately after an upward step-wise change of temperat
21、ure,the PMV model predicts well the thermal sensation,while it takes around 20 min at temperature down-steps .Field studies in warm climates in buildings without air-conditioning have shown,however,that the PMV model predicts a warmer thermal sensation than the occupants actually feel. For such non-
22、air-conditioned buildings an adaptive model has been proposed. This model is a regression equation that relates the neutral temperature indoors to the monthly average temperature outdoors. The only variable is thus the average outdoor temperature,which at its highest may have an indirect impact on t
23、he human heat balance. An obvious weakness of the adaptive model is that it does not include human clothing or activity or the four classical thermal parameters that have a well-known impact on the human heat balance and therefore on the thermal sensation. Although the adaptive model predicts the th
24、ermal sensation quite well for non-air-conditioned buildings of the 1900s located in warm parts of the world,the question remains as to how well it would suit buildings of new types in the future where the occupants have a different clothing behaviour and a different activity pattern.Why then does t
25、he PMV model seem to overestimate the sensation of warmth in non-air-conditioned buildings in warm climates?There is general agreement that physiological acclimatization does not play a role. One suggested explanation is that openable windows in naturally ventilated buildings should provide a higher
26、 level of personal control than in air-conditioned buildings. We do not believe that this is true in warm climates. Although an openable window sometimes may provide some control of air temperature and air movement,this applies only to the persons who work close to a window. What happens to persons
27、in the office who work far away from the window?We believe that in warm climates air-conditioning with proper thermostatic control in each space provides a better perceived control than openable windows.Another factor suggested as an explanation to the difference is the expectations of the occupants
28、. We think this is the right factor to explain why the PMV overestimates the thermal sensation of occupants in non-air-conditioned buildings in warm climates. These occupants are typically people who have been living in warm environments indoors and outdoors,maybe even through generations. They may
29、believe that it is their “destiny” to live in environments where they feel warmer than neutral. This may be expressed by an expectancy factor,e. The factor e may vary between 1 and 0.5. It is 1 for air-conditioned buildings. For non-air-conditioned buildings,the expectancy factor is assumed to depen
30、d on the duration of the warm weather over the year and whether such buildings can be compared with many others in the region that are air-conditioned. If the weather is warm all year or most of the year and there are no or few other air-conditioned buildings,e may be 0.5,while it may be 0.7 if ther
31、e are many other buildings with air-conditioning. For non-air-conditioned buildings in regions where the weather is warm only during the summer and no or few buildings have air-conditioning,the expectancy factor may be 0.7 to 0.8,while it may be 0.8 to 0.9 where there are many air-conditioned buildi
32、ngs. In regions with only brief periods of warm weather during the summer,the expectancy factor may be 0.9 to 1. Table 1 proposes a first rough estimation of ranges for the expectancy factor corresponding to high,moderate and low degrees of expectation.ExpectationClassification of buildingsExpectanc
33、yfactor,eHighNon-air-conditioned buildings located in regions where air-conditioned buildings are common. Warm periods occurring briefly during the summer season.0.9 - 1.0ModerateNon-air-conditioned buildings located in regions with some air-conditioned buildings. Warm summer season.0.7 - 0.9LowNon-
34、air-conditioned buildings located in regions with few air-conditioned buildings. Warm weather during all seasons.0.5 - 0.7Table 1. Expectancy factors for non-air-conditioned buildings in warm climates.A second factor that contributes to the difference between the PMV and actual thermal sensation in
35、non-air-conditioned buildings is the estimated activity. In many field studies in offices,the metabolic rate is estimated on the basis of a questionnaire identifying the percentage of time the person was sedentary,standing,or walking. This mechanistic approach does not acknowledge the fact that peop
36、le,when feeling warm,unconsciously tend to slow down their activity. They adapt to the warm environment by decreasing their metabolic rate. The lower pace in warm environments should be acknowledged by inserting a reduced metabolic rate when calculating the PMV.To examine these hypotheses further,da
37、ta were downloaded from the database of thermal comfort field experiments. Only quality class II data obtained in non-air-conditioned buildings during the summer period in warm climates were used in the analysis. Data from four cities (Bangkok,Brisbane,Athens,and Singapore) were included,representin
38、g a total of more than 3200 sets of observations . The data from these four cities with warm climates were also used for the development of the adaptive model.For each set of observations,recorded metabolic rates were reduced by 6.7% for every scale unit of PMV above neutral,i.e. a PMV of 1.5 corres
39、ponded to a reduction in the metabolic rate of 10%. Next,the PMV was recalculated with reduced metabolic rates using ASHRAEs thermal comfort tool . The resulting PMV values were then adjusted for expectation by multiplication with expectancy factors estimated to be 0.9 for Brisbane,0.7 for Athens an
40、d Singapore and 0.6 for Bangkok. As an average for each building included in the field studies,Figure 1 and Table 2 compare the observed thermal sensation with predictions using the new extended PMV model for warm climates.Comparison of observed mean thermal sensation with predictions made using the
41、 new extension of the PMV model for non-air-conditioned buildings in warm climates. The lines are based on linear regression analysis weighted according to the number of responses obtained in each building.CityExpectancyfactorPMV adjusted toproper activityPMV adjustedfor expectationObservedmean vote
42、Bangkok0.62.01.21.3Singapore0.71.20.80.7Athens0.71.00.70.7Brisbane0.90.90.80.8Table 2. Non-air-conditioned buildings in warm climates. Comparison of observed thermal sensation votes and predictions made using the new extension of the PMV model.The new extension of the PMV model for non-air-condition
43、ed buildings in warm climates predicts the actual votes well. The extension combines the best of the PMV and the adaptive model. It acknowledges the importance of expectations already accounted for by the adaptive model,while maintaining the PMV models classical thermal parameters that have direct i
44、mpact on the human heat balance. It should also be noted that the new PMV extension predicts a higher upper temperature limit when the expectancy factor is low. People with low expectations are ready to accept a warmer indoor environment. This agrees well with the observations behind the adaptive mo
45、del.Further analysis would be useful to refine the extension of the PMV model,and additional studies in non-air-conditioned buildings in warm climates in different parts of the world would be useful to further clarify expectation and acceptability among occupants. It would also be useful to study th
46、e impact of warm office environments on work pace and metabolic rate.ConclusionsThe PMV model has been validated in the field in buildings with HVAC systems,situated in cold,temperate and warm climates and studied during both summer and winter. In non-air-conditioned buildings in warm climates,occup
47、ants may perceive the warmth as being less severe than the PMV predicts,due to low expectations.An extension of the PMV model that includes an expectancy factor is proposed for use in non-air-conditioned buildings in warm climates.The extended PMV model agrees well with field studies in non-air-cond
48、itioned buildings in warm climates of three continents.Thermal comfort and air quality in a building should be considered simultaneously. A high perceived air quality requires moderate air temperature and humidity.AcknowledgementFinancial support for this study from the Danish Technical research Council is gratefully acknowledged.ReferencesAndersson,L.O.,Frisk,P.,Lfst