BWDK-S干式变压器温度控制仪 使用说明书
BWDK-S Dry-type Transformer Temperature Controller Operation Instructions
BWDK-S系列
BWDK-S Series of
干式变压器温度控制仪
Dry-type Transformer Temperature Controller
使用说明书
Operation Instructions
制造单位:南京圣尚科技有限公司
Manufactured by: Nanjing Shengshang Science & Technology Co., Ltd.
地址:南京黑龙江路32号
Address: No. 32, Heilongjiang Road, Nanjing
邮编:210037
Zip code:210037
电话:025-83345450 13605180030
Tel: 025-83345450 13605180030
联系人:彭永滨
Contact: Peng Yongbin
警告:主体变压器做高压绝缘实验时,请断开与本温控仪间的联线,以确保温控仪安全。
Warning: When conduct the high-voltage insulation test to the main body of transformer, please disconnect it from the temperature controller so as to ensure the safety of the temperature controller.
一、 概述 Outline
BWDK-S系列干式变压仪温度控制仪是由微处理器构成的智能仪器,它使用三只铂电阻作传感器,测量干式变压器三相绕组的温度。根据设定的温度值,启停风机进行温度控制。仪器具有各种声光报警功能,是保护干式变压器的重要装置。
BWDK-S series of dry-type transformer temperature controller is an intelligent instrument equipped with a microprocessor. It uses three platinum resistances as sensors to measure the temperature of three-phase windings of the dry-type transformer, and start and stop the fan for temperature control according to preset temperature value. With various sound and light alarm functions, the instrument is an important device for protecting the dry-type transformer.
仪器符合JB/T7631-2005标准。 The instrument complies with Standard JB/T7631-2005.
仪器具有以下特点: The instrument has features as follows:
1. 仪器可以测量干式变压器三相绕组的温度,用LED每隔4秒循环显示三相温度值或定点显示三相温度最大值。
It is capable of measuring the temperature of three-phase windings of the dry-type transformer, displaying in turn three-phase temperature values with a LED every 4 seconds or displaying the highest three-phase temperature periodically.
2. 仪器可以用按键输入4种温度设定值。当测量温度超过各设定值时,分别控制风机启停、超温报警、超高温跳闸等。温度设定值可以随时修改,断电后不会消失。
Four preset temperature values can be input by keystroke. When the measured temperature exceeds preset values, the instrument will respectively control startup and stop of the fan, over-temperature alarm, ultra-high temperature trip, etc. The preset temperature values can be modified at any time, and will remain after the instrument is switched-off.
3. 仪器具有传感器断线故障检测功能。
The instrument is capable of detecting the broken-line fault of the sensor.
4. 仪器具有风机依设定温度自动定时启动和手动启动功能。仪器可设定1-250小时内自动启动风机1分钟。
The instrument has the function of automatic timing startup and manual startup according to the preset temperature, and can set automatic fan startup for 1 minute within 1-250 hours.
5. 仪器具有温度历史最大值记录功能。
The instrument is capable of remembering the highest temperature ever occurred.
6. 根据使用需要,仪器可以提供数字量或模拟量输出。
The instrument is capable of providing digital or analog output as required.
7. 仪器面板上有绿色的状态指示灯,风机运转指示灯为黄色,而超温、故障和跳闸状态指示灯为红色。
There is a green status indicator light on the instrument panel. The indicator light turns yellow when the fan operates and turns red at the status of over-temperature, fault and trip.
二、技术特性 Technical specifications
1. 仪器连续工作环境:温度:0~50℃;相对湿度:小于90%RH(25℃)。
Conditions for continuous operation of the instrument: Temperature: 0~50℃, relative humidity: less than 90%RH(25℃).
短时间工作环境:温度:-50~75℃。
Conditions for short-time operation of the instrument: Temperature: -50~75℃.
2. 工作电源:AC220V±10%;频率50Hz±4%。仪表保护装置5A熔丝。
Working power supply: AC220V±10%, frequency 50Hz±4%. A 5A fuse for the instrument protector.
3. 温度测量范围:-50~200℃。
Temperature measurement range: -50~200℃.
4. 温度测量准确度:0.5级。
Temperature measurement precision: Class 0.5.
5. 显示方式:LED每隔4秒循环显示A、B、C三相温度或定点显示三相温度的最大值,分辨力为0.1℃。
Display mode: A LED displays temperature of Phase A, B and C in turn every 4 seconds, or displays the highest three-phase temperature periodically, with resolution being 0.1℃.
6. 输出方式:输出报警、跳闸和传感器故障,继电器接点容量AC250V/10A。
Output mode: Output alarm, trip and sensor fault. Relay contact capacity is AC250V/10A.
7. 启动风机:控制4~6台风机,继电器接点总容量AC250V/30A。
Fan startup: Control 4-6 fans, and total relay contact capacity is AC250V/30A.
8. 耐压实验:2500VAC、60Hz、60秒。
Withstanding-voltage test: 2500VAC, 60Hz and 60 seconds.
9. 外形尺寸:80(H)×160(W)×130(D)mm3。
Dimensions: 80(H)×160(W)×130(D)mm3.
10.开孔尺寸:76(H)×152(W)mm2
Perforate dimensions: 76(H)×152(W)mm2.
11.模拟量输出:三路4-20mA,对应A、B、C相温度0-200℃,或一路4-20mA对应A、B、C相中最大值温度0-200℃,精度1%±1个字,负载电阻≤600Ω。
Analog output: Three-line 4-20mA output corresponds with temperature of Phase A, B and C (0-200℃), or one-line 4-20mA output corresponds with the highest temperature of 0-200℃ among Phase A, B and C. Precision is within 1%±1 and load resistance is ≤600Ω.
12.数字量输出:RS232或RS485串行通讯接口,采用Modbus通讯协议。
Digital output: RS232 or RS 485 serial communication interface, with Modbus Communication Protocol being adopted.
三、仪器结构 Instrument structure
1. 前面板说明图(见图1) Front panel illustration: (See Figure 1)
图1 Figure 1
前面板上有两组数码管,I数码管显示A、B、C,II数码管显示对应的该相温度。面板上排共6个指示灯。当“巡回”指示灯亮时,表示仪器巡回显示三相温度;当“最大值”指示灯亮时,表示仪器显示当前最大值温度及其对应相。“跳闸”、“超温”、“故障”、“风机”指示灯分别指示跳闸、超温、故障、风机的状态。
There are two groups of digital tubes on the front panel, with Digital Tube I displaying character A, B or C, and Digital Tube II displaying corresponding phase temperature. There are totally 6 indicator lights above the LED. When the “Circuit” light is on, it indicates the instrument displays three-phase temperature in turn. When the “Max. value” light is on, it indicates that the instrument displays the current highest temperature and its corresponding phase. Lights of “Trip”, “Over-temperature”, “Fault” and “Fan” respectively indicate the status of trip, over-temperature, fault and fan.
2. 温度传感器的接线 Connection of temperature sensor
三只铂电阻通过一个9芯插座引出,引线长度见图2:
Three platinum resistances are led out through a 9-core socket. The lead length is shown in Figure 2.
图2 Figure 2
四、输出控制动作说明 Description of output control action
仪器测量出变压器三相绕组的温度,求出其中的最大值Cmax,将最大值与四种温度设定值C1,C2,C3,C4相比较,然后控制风机启停、超温报警、超高温跳闸等动作。C1,C2,C3,C4的定义及出厂设定值见表1,输出控制见表2.
After the instrument measures the temperature of three-phase windings of the transformer, calculate the maximum Cmax among them, and compare the maximum value with the four preset value of C1,C2,C3 and C4 before controlling the startup and stop of fan, over-temperature alarm, ultra-high temperature trip and other actions. The definitions of C1,C2,C3 and C4 as well as ex-work preset values are shown in Table 1 and output control is shown in Table 2.
表1 C1,C2,C3,C4的定义及出厂设定值
Table 1 Definitions of C1,C2,C3 and C4 and Ex-work Preset Values
C1
C2
C3
C4
定 义
Definition
风机停温度
Temperature for fan stop
风机开温度
Temperature for fan startup
超温报警温度
Temperature for over-temperature alarm
超温跳闸温度
Temperature for over-temperature trip
出厂值(℃)
Ex-work value(℃)
80
100
130
150
表2 输出控制
Table 2 Output Control
序号
Serial no.
工作状态
Working status
测量和计算结果
Measurement and calculation results
指示灯状态
Light status
控制动作
Control action
1
风机启停上行程
Up stroke for fan startup and stop
Cmax≥C2
风机灯亮
“Fan” on
风机启
Fan starts
风机启停下行程
Down stroke for fan startup and stop
C1≥Cmax
风机灯灭
“Fan” off
风机停
Fan stops
2
超温报警
Over-temperature alarm
Cmax≥C3
风机灯亮
“Fan” on
超温灯亮
“Over-temperature” on
风机启
Fan starts
超温继电器吸合
Over-temperature relay on
3
超温跳闸
Over-temperature trip
Cmax≥C4
风机灯亮
“Fan” on
超温灯亮
“Over-temperature” on
跳闸灯亮
“Trip” on
风机启
Fan starts
超温继电器吸合
Over-temperature relay on
跳闸继电器吸合
Trip relay on
4
传感器断线
Sensor break
显示HHHH
HHHH displayed
故障灯亮
“Fault” on
故障继电器吸合
Fault relay on
五. 基本功能使用方法 Operation methods of basic functions
1. 接通仪器电源后,巡回显示三相绕组的温度,同时根据测量结果输出各种控制信号,见表2。
After the instrument is energized, temperature of three-phase windings is displayed in turn. In the meantime, various control signals are output in accordance with measurement results. Please see Table 2.
2. 按键的定义和功能
Definitions & functions of keystrokes
∧:加1键,每按一次,输入参数加1,继续按下时,输入参数连续加1。测量时为巡回显示与最大值显示的转换键。
∧:Adding 1 key. Every time you press this key, the input parameter value adds 1. If you keep the key pressed, the input parameter value will continuously increase by 1. It acts as a switch key between circuit display and maximum value display in time of measurement.
∨:减1键,每按一次,输入参数减1,继续按下时,输入参数连续减1。测量时当三相最大值温度小于C2时,按下此键,手动打开或关闭风机。
∨:Subtracting 1 key. Every time you press this key, the input parameter value subtracts 1. If you keep the key pressed, the input parameter value will continuously decrease by 1. When the highest temperature of three-phase is less than C2 in time of measurement, press this key to manually turn on or turn off the fan.
@:输入转换键,每按一次,进入下一个参数的检查和修改。测量时按下此键,进入监控状态。
@:Input switch key. Every time you press this key, you can enter the examination and modification of next parameter. Press this key to enter into monitoring status in time of measurement.
3. 检查参数的方法(操作流程图)
Methods for parameter examination (See Operation Flowchart)
仪器的基本参数共有8个。提示符分别为C1、C2、C3、C4、Ft、Ht、Ad、Bp。
The instrument has totally 8 basic parameters, with indication symbols being C1, C2, C3, C4, Ft, Ht, Ad and Bp respectively.
C1、C2、C3、C4的定义见表1,Ft为风机定期检测的时间间隔,单位为小时,最大值为250小时,每次开启风机时间约1分钟,若设置为0则无此功能;Ht为所测量三相温度的历史最大值。Ad为通讯地址提示符,Bp为通讯波特率。
Definitions of C1, C2, C3 and C4 are shown in Table 1. Ft represents the interval of periodic examination of the fan, with unit being an hour and the max. value being 250 hours. Time for fan startup is about 1 minute, and the function will not exist if 0 is set. Ht is the max. historical value measured for the three-phase temperature. Ad is an indication symbol of communication address and Bp is communication baud rate.
检查参数的具体方法 Specific methods for examining parameters
仪器通电显示版本号SS03后立即进入测量状态,此时连续按下@键,则按C1、C2、C3、C4、Ft、Ht、Ad、Bp的顺序显示各个参数的设定值。
After the version no. SS03 is displayed following electrification, the instrument immediately enters the measuring state. At this time, press Key @ continuously, the preset values of various parameters will be displayed in the order of C1, C2, C3, C4, Ft, Ht, Ad and Bp.
这些参数值只能检查不能修改。当持续5秒未有键按下,自动回到测量状态。
These parameters can be examined but cannot be modified. If there is no key pressed continuously for 5 seconds, the instrument returns to the measuring state.
4. 修改参数的方法(见操作流程图) Methods for modifying parameters (See Operation flowchart)
当仪器处于测量状态时,按下@键大于15秒钟,仪器I数码管右下角显示小数点,II数码管显示提示符C1,按@键后显示C1的数值,再按∧∨键可以修改C1的数值,按下@键进入下一个提示符C2,再按下@键显示C2的数值,按∧∨键可以修改C2的数值,依此类推……
When the instrument is at the measuring state, hold Key @ for about 15 seconds, a decimal will be displayed at the bottom right corner of the Digital Tube I of the instrument and the indication symbol C1 will be displayed on the Digital Tube II. Value of C1 will be displayed after pressing Key @, and value of C1 can be modified by pressing Key ∧ and ∨. Press Key @to enter the next indication symbol C2. Press Key @again, the instrument will display the value of C2. Press Key ∧ and ∨, value of C2 can be modified, and so on.
5. 手动风机的工作方法 Methods for manually operating the fan
仪器处于测量状态,且温度低于C2时按∨键则打开风机,再按一次则停止风机。
When the instrument is at the measuring state and the temperature is less than C2, press Key ∨ to turn on the fan and press again to turn off it.
6. 选择显示方式 Select display mode
仪器处于测量状态,按下∧键,显示方式在巡回显示和最大值显示之间进行切换,相应的巡回显示指示灯和最大值显示指示灯分别点亮。
When the instrument is at the measuring state, press Key ∧, the display mode will switch between the circuit and max. value modes. And the corresponding MAX. or Circuit light will be on.
六、仪表后盖接线示意图 Model of instrument and wiring diagram
七、常见故障排除方法
故障现象
故障原因及维修方法
不显示温度
① 仪器没有输入电源,请检查供电是否正常,即后端子①、②处是否有AC220V电压。
② 电源开关不通,请检查电源开关是否处于接通位置,并且接触良好。
③ 电源变压器断线或损坏,请更换之。
温度指示异常
或显示HHHH
① 传感器断线或损坏,请更换连线或传感器。
② 传感器未接牢,将传感器接插件上紧。
③ 数据采集电路有故障,将通知本公司。
设定数据不能修改
① 持续按@键时间太短,请持续按@键大于10秒钟。
② 按键不起作用,请更换按键。
风机灯亮后
风机不转
① 风机有短路、开路现象,请检查更换有故障风机。
② 检查保险丝是否烧断,若已烧坏,请更换之。
三相温度显示
偏差大
① 变压器三相温度不同,是正常现象。
② 三支铂电阻放置位置不同,应该重新调整位置使其一致。
八、本公司产品由于采用新型抗干扰设计,确保仪表在各种条件下均能长期可靠正常工作。本公司产品实行两年“三包服务”(包修、包换、包退)。